Michigan Journeyman Electrical Sign
Contractor License Practice Guide 80
Questions and Verified Solutions Exam
2026/2027
1. Where PV system DC circuits are run inside a building, they shall be contained in
metal race ways ,____ or metal enclosures from the point of penetration of the surface
of the building to the readily accessible disconnecting means. - Correct Answer-Type
MC cable 690.31.G
2. Unless specifically listed and marked for the location, the coupling means of the
electric vehicle supply equipment shall be stored or located at a height of not less
than___ inches above the grade level for outdoor locations. - Correct Answer-24' 625.50
3. Unless specifically listed and marked for the location, the coupling means of the
electric vehicle supply equipment shall be stored or located at a height of not less
than___ inches above the floor level for indoor locations. - Correct Answer-18" 625.50
4. All 15 and 20 ampere, 125 volt non locking type receptacles installed in the vehicle
washing area of a carwash shall be listed and so identified as___ type. - Correct
Answer-weather resistant 406.9.B1
5. All 15 and 20 ampere, 125 volt non locking type receptacles installed in the vehicle
washing area of a carwash shall have an enclosure that is____ whether or not the
attachment plug cap is inserted - Correct Answer-weather proof 406.9.B
6. An individual, other than an individual who is licensed under this article and___ and
working under the direction of a holder of an electrical contractor's license, shall not in
any manner undertake to execute any electrical wiring. - Correct Answer-employed by
PA.407 339.5737
7. The ratio of electrical journeyman or master electricians to registered apprentice
electricians shall be on the basis of___ electrical journeyman or master electricians to
no more than___ registered apprentice electricians. - Correct Answer-1 to 3 PA.407
339.5717 sec 717.3
8. Who can obtain a sign specialty contractor's license? - Correct Answer-an individual
whom holds a sign specialist license
Michigan
, Michigan
9. Where fuses rated___ amperes or higher are installed, the fuse shall have a clearing
time of 0.07 seconds or less at the available arcing current. - Correct Answer-1200amps
240.67.B
10. A meeting room that is at least 12 feet wide and has a floor area of at least 215
square feet shall have at least___ receptacle outlet(s) located in the floor at a distance
not less than 6 feet from any fixed wall for each 215 square feet or major portion of floor
space. - Correct Answer-1 210.71.B2
11. For a commercial building the service disconnecting means shall have a rating of
not less than___ amperes - Correct Answer-60amps 230.79.D
12. The small appliance branch circuit may also provide a receptacle to provide power
for supplemental equipment and lighting on____ - Correct Answer-gas fired ranges or
ovens 210.50.B2
13. Where type NM cable is fastened within___ inches of the box securing the cable to
the box shall not be required. - Correct Answer-12" 314.17 exc C
14. Pool associated motors shall be permitted to employ cord and plug connections.
The flexible cord shall___? - Correct Answer-not exceed 3' in length 680.8.A
15. The length of the cord for a built-in dishwasher shall be___? - Correct Answer-3' to
6.5' 422.16.B.2.3
16. All 15 and 20-ampere, 125 and 250-volt non-locking type receptacles shall be listed
tamper resistant receptacles when installed in? - Correct Answer-elementary schools
17. A 1-inch conduit contains three 3-wire circuits. All conductors are # 10 TW. Each
circuit consists of two phase conductors, one neutral conductor that carries only the
unbalanced current, and one equipment grounding conductor. The maximum ampacity
of each phase conductor is___ amperes - Correct Answer-30amps
18. A kiln rated 6000 watts, 208 volts, 3 phase draws___ amperes. - Correct Answer-
16.67amps
19. An Expansion joint is required for PVC conduit. When the temperature changes
from -5° to 100°F, the thermal expansion for 100 feet of Rigid PVC conduit is___ inches
- Correct Answer-4.26 t352.44
20. The allowable ampacity of a #12 AWG THHN copper conductor is___ a. - Correct
Answer-30a
21. The maximum overcurrent protection for a circuit containing #12 AWG THHN
copper conductors is___ amperes - Correct Answer-20a small conductor rule 240.4.D5