◉What is the minimum branch circuit size for a Level II EVSE with a
32-ampere current rating?
Select one:
a.32 A
b.35 A
c.40 A
d.55 A. Answer: c.40 A
32 A × 1.25 = 40 A minimum OCPD
◉Two Level II EVSE circuits are installed in the same PVC conduit.
Each EVSE is served by a 40-ampere circuit at 240 volts with an EGC
run along with the circuits. What size copper EGC is required for this
installation?
Select one:
a.10 AWG
b.8 AWG
c.6 AWG
, d.4 AWG. Answer: a.10 AWG
Note: T250.122 - 40 A Circuit = 10 AWG CU equipment ground
◉A 32,000 square foot office building has 120 20-ampere, 120-volt
duplex receptacle outlets. What is the branch circuit receptacle load?
Select one:
a.9,600 VA
b.21,600 VA
c.28,000 VA
d.32,000 VA. Answer: d.32,000 VA
Note: 220.14(K) - use largest of either 1 VA per square foot or 180
VA per outlet.
180 VA × 120 = 21,600 VA32,000 ft2 × 1
VA = 32,000 VA
◉An existing 400-ampere, 120/208-volt, 3-phase, 4-wire service
has 30 kilovolt-amperes of non-continuous load and 58 kilovolt-
amperes of continuous load. How much more continuous load can
be added to the service? (Note: Use 1.732 for the square root of 3.)