CERTIFIED HEALTHCARE FACILITY MANAGER (CHFM
) EXAM
Vertical openings connecting four or more floors require ? rated walls - Answers :2 hour
Maintaining equipment for extinguishing fires.
limited area sprinkler systems- connected to domestic water supply must have a _____
and have nor more than ______ sprinkler heads - Answers :shut off valves/6(six)
Fire alarm systems. The fire alarm signal automatically transmits to one of the following
(four choices) - Answers :1) auxiliary fire alarm system with direct connection to the
servicing FD
2) central station service as described in NFPA 72
3) proprietary supervising station system
4) remote supervising station fire alarm system
Existing labs, that are not a severe hazard require ______ walls and _____ rated doors
(new only need what) - Answers :1 hour/ 3/4 hour/ resist passage or smoke
Icons used in the HAS manual- Scoring categories.
Category A- usually related to ________
Category C- are - Answers :a- usually related to structural requirements (policies,
programs or plans) addresses issues that must be fully compliant
c- are frequency based requirements and are scored lowered on the number of times a
hospital is found not to be compliant with a particular EP
New and existing vertical openings require a __________ rated enclosure as long as
there are _______ stories or less - Answers :1 hour/ 3 stories
Hazardous areas such as boiler rooms fuel fired heater rooms, bulk laundires (larger
than 100 sq ft) require a ________ rated walls and a _______ rated door - Answers :1
hour/3/4 hours
flamable liquid storage terms. new and existing, require _____ rated walls and _____
rated doors - Answers :2 hour/1 1/2 hour
Travel distance from any point to the nearest fire extinguisher is ________ or less -
Answers :75'
Soiled linens and trash receptacles larger than 32 gallons must be located in a room
protected as a ________ - Answers :hazardous area (1 hour rated walls, 3/4 hour rated
doors)
New elevators must be equipped with the following four items - Answers :1) firefighter
service key and smoke detector automatic recall
) EXAM
Vertical openings connecting four or more floors require ? rated walls - Answers :2 hour
Maintaining equipment for extinguishing fires.
limited area sprinkler systems- connected to domestic water supply must have a _____
and have nor more than ______ sprinkler heads - Answers :shut off valves/6(six)
Fire alarm systems. The fire alarm signal automatically transmits to one of the following
(four choices) - Answers :1) auxiliary fire alarm system with direct connection to the
servicing FD
2) central station service as described in NFPA 72
3) proprietary supervising station system
4) remote supervising station fire alarm system
Existing labs, that are not a severe hazard require ______ walls and _____ rated doors
(new only need what) - Answers :1 hour/ 3/4 hour/ resist passage or smoke
Icons used in the HAS manual- Scoring categories.
Category A- usually related to ________
Category C- are - Answers :a- usually related to structural requirements (policies,
programs or plans) addresses issues that must be fully compliant
c- are frequency based requirements and are scored lowered on the number of times a
hospital is found not to be compliant with a particular EP
New and existing vertical openings require a __________ rated enclosure as long as
there are _______ stories or less - Answers :1 hour/ 3 stories
Hazardous areas such as boiler rooms fuel fired heater rooms, bulk laundires (larger
than 100 sq ft) require a ________ rated walls and a _______ rated door - Answers :1
hour/3/4 hours
flamable liquid storage terms. new and existing, require _____ rated walls and _____
rated doors - Answers :2 hour/1 1/2 hour
Travel distance from any point to the nearest fire extinguisher is ________ or less -
Answers :75'
Soiled linens and trash receptacles larger than 32 gallons must be located in a room
protected as a ________ - Answers :hazardous area (1 hour rated walls, 3/4 hour rated
doors)
New elevators must be equipped with the following four items - Answers :1) firefighter
service key and smoke detector automatic recall