Vertical openings connecting four or more floors require? rated walls CORRECT ANSWER 2 hour New and existing vertical openings require a __________ rated enclosure as long as there are _______ stories or less CORRECT ANSWER 1 hour/ 3 stories Hazardous areas such as boiler rooms fuel fired heater rooms, bulk laundries (larger than 100 sq. ft.) require a ________ rated walls and a _______ rated door CORRECT ANSWER 1 hour/3/4 hours flammable liquid storage terms. new and existing, require _____ rated walls and _____ rated doors CORRECT ANSWER 2 hour/1 1/2 hour Existing labs, that are not a severe hazard require ______ walls and _____ rated doors (new only need what) CORRECT ANSWER 1 hour/ 3/4 hour/ resist passage or smoke Icons used in the HAS manual- Scoring categories. Category A- usually related to ________ Category C- are CORRECT ANSWER a- usually related to structural requirements (policies, programs or plans) addresses issues that must be fully compliant c- are frequency based requirements and are scored lowered on the number of times a hospital is found not to be compliant with a particular EP