⩥ (5.2.1.1) The automatic and manual means of system actuation,
external to the control head or releasing device, shall be. Answer:
separate and independent of each other so that a failure of one will not
impair the operation of the other
⩥ (5.2.1.2) The manual means of system activation shall be permitted to
be common with the automatic means if the. Answer: manual activation
device is located between the control head or releasing device and the
first fusible link
⩥ (5.2.1.4) All devices necessary for proper operation of the system
shall function. Answer: simultaneously with the system operation
⩥ (5.2.1.5) Operation of any manual actuator shall be all. Answer: that is
required to bring about the full operation of the system
,⩥ (5.2.1.6) At least one manual actuator. Answer: shall be provided for
each system
⩥ (5.2.1.7) All operating devices shall designed, located, installed, or
protected so that. Answer: they are not subject to mechanical,
environmental, or other conditions that could render them inoperative or
cause inadvertent operation of the system
⩥ (5.2.1.8) An audible or visual indicator shall be provided. Answer: to
show that the system has operated, that personnel response is needed,
and that the system is in need of recharge
⩥ (5.2.1.9) The extinguishing system shall be connected to the fire alarm
systems, if provided, in accordance with the requirements of NFPA 72.
Answer: so that the actuation of the extinguishing system will sound the
fire alarm
⩥ (5.2.1.10) At least one manual actuation device shall be located in.
Answer: a means of egress or at a location acceptable to the authority
having jurisdiction
⩥ (5.2.1.10.1) Each manual actuation device shall be installed no more
than. Answer: 48in (1200mm) and no less than 42in (1067mm) above
the floor
, ⩥ (5.2.1.10.2) The manual actuation device shall clearly. Answer:
identify the hazard protected and provide instructions for its use
⩥ (5.2.1.12) Automatic systems protection only common exhaust ducts.
Answer: shall not require a manual actuator
⩥ (5.2.1.13) The means for manual actuation shall be. Answer:
mechanical and shall not rely on electrical power for actuation
⩥ (5.2.1.14) Electrical power shall be permitted to be used for manual
actuation if. Answer: electrical supervision and a reserve power supply
are provided in accordance with 5.3.1
⩥ (5.3.1) Where electrical power is required to operate the fixed
automatic fire-extinguishing system,. Answer: the system shall be
monitored by a supervisory alarm with a reserve power supply provided
⩥ (5.3.1.1) Where supervision of any or all of the following is provided,
it shall be designed and installed to give an indication of trouble in the
following:. Answer: 1. Automatic detection system
2. Electrical actuation circuit
3.Electrical power supply
SIX ACTUAL EXAMINATION SCRIPT
PROFESSIONAL REVIEW 2026 COMPLETE
FIFTY NINE QUESTIONS AND CORRECT
ANSWERS ALREADY PASSED
GUARANTEED PASS
⩥ (5.2.1.1) The automatic and manual means of system actuation,
external to the control head or releasing device, shall be. Answer:
separate and independent of each other so that a failure of one will not
impair the operation of the other
⩥ (5.2.1.2) The manual means of system activation shall be permitted to
be common with the automatic means if the. Answer: manual activation
device is located between the control head or releasing device and the
first fusible link
⩥ (5.2.1.4) All devices necessary for proper operation of the system
shall function. Answer: simultaneously with the system operation
⩥ (5.2.1.5) Operation of any manual actuator shall be all. Answer: that is
required to bring about the full operation of the system
,⩥ (5.2.1.6) At least one manual actuator. Answer: shall be provided for
each system
⩥ (5.2.1.7) All operating devices shall designed, located, installed, or
protected so that. Answer: they are not subject to mechanical,
environmental, or other conditions that could render them inoperative or
cause inadvertent operation of the system
⩥ (5.2.1.8) An audible or visual indicator shall be provided. Answer: to
show that the system has operated, that personnel response is needed,
and that the system is in need of recharge
⩥ (5.2.1.9) The extinguishing system shall be connected to the fire alarm
systems, if provided, in accordance with the requirements of NFPA 72.
Answer: so that the actuation of the extinguishing system will sound the
fire alarm
⩥ (5.2.1.10) At least one manual actuation device shall be located in.
Answer: a means of egress or at a location acceptable to the authority
having jurisdiction
⩥ (5.2.1.10.1) Each manual actuation device shall be installed no more
than. Answer: 48in (1200mm) and no less than 42in (1067mm) above
the floor
, ⩥ (5.2.1.10.2) The manual actuation device shall clearly. Answer:
identify the hazard protected and provide instructions for its use
⩥ (5.2.1.12) Automatic systems protection only common exhaust ducts.
Answer: shall not require a manual actuator
⩥ (5.2.1.13) The means for manual actuation shall be. Answer:
mechanical and shall not rely on electrical power for actuation
⩥ (5.2.1.14) Electrical power shall be permitted to be used for manual
actuation if. Answer: electrical supervision and a reserve power supply
are provided in accordance with 5.3.1
⩥ (5.3.1) Where electrical power is required to operate the fixed
automatic fire-extinguishing system,. Answer: the system shall be
monitored by a supervisory alarm with a reserve power supply provided
⩥ (5.3.1.1) Where supervision of any or all of the following is provided,
it shall be designed and installed to give an indication of trouble in the
following:. Answer: 1. Automatic detection system
2. Electrical actuation circuit
3.Electrical power supply