In-line check valves shall have threaded purge points of 1/8 inch
____ NPT
Mains & branches in medical gas systems shall be no less 1/2 inch
than ____
Drops to station outlets and inlets shall be no less than 1/2 inch
____ NPS
Copper outlet tubes on station inlets shall be no less than 1/2 inch
____ O.D.
Connecting tubing for gauges and alarm devices shall be 1/4 inch
permitted to be ____ NPS
Category 1 Dental Facilities utilizing General anesthesia & Deep sedation
Instrument air standby headers shall be sufficient for ____ 1 hour
of normal operation from attached cylinder
Reserves cylinders for Liquid Ring compressors shall be 1-hour
sufficient for ____ normal operation, when installed
Quality of medical air shall not have permanent 1 Micron
particulates sized ____ or larger in the air
Defective joints are allowed to be reheated ____ time one
before it must be replaced
Manufactured assemblies are subject to a standing 1%
pressure test to ensure a less than ____ loss in pressure
Oxygen analyzers shall read that there is less than ____ 1% oxygen
concentration in the system before any brazing can begin
Fittings may be re-cleaned on-site using a solution of ____ 1
pound of sodium carbonate to 3 gallons of water
Category ____ space is one in which failure of equipment 1
or a system is likely to cause major injury or death of
patients, staff, or visitors
Only ____ service valve is required off the riser for each one
branch
, Med Gas Installer 6010 Exam
The installation of cryogenic fluid central supply systems M-1
shall be compliant with CGA ____
The outdoor location of bulk cryogenic liquid central M-1
systems shall be compliant with CGA ____
Reciprocating compressors shall provide an inspection 1.5
opening no smaller than ____ shaft diameter in size
Category dental 2 initial pressure test for oxygen and 1.5
nitrous oxide shall ____ times operating pressure
Instrument air filters shall be sized to allow for ____ of 100%
system design peak demand
Flammable liquid has a flash point below ____ degrees 100
Fahrenheit
Final line pressure regulators shall be sized for ____ of 100%
peak demand
EOSC shall have an inlet that allows for ____ of the 100%
system demand
Medical air filters shall be sized for ____ system peak 100%
demand
Medical aid dryers used in medical air compressors shall 100%
be sized for ____ of peak demand
NFPA ____ is the life and safety code for med gas facilities 101
Cylinders in use and in storage shall be prevented from 125
reaching temperatures in excess of ____ degrees
Fahrenheit
Medical gas piping may be located within tunnels with fuel 130
gas lines or electrical lines if the ambient temperature is
limited to ____ degrees Fahrenheit
Initial pressure test shall be ____ times the operating 1.5, 150 psi
pressure but no less than ____ gauge pressure
Manufactures assemblies hose or flexible connectors shall 1000 psi
have a minimum burst pressure of ____
, Med Gas Installer 6010 Exam
Metallic and non-metallic flex connectors shall have a 1000 psi
minimum burst pressure of ____
Medical gas rails (MGR) shall have a melting point of at 1000 degrees Fahrenheit
least ____
Central supply systems for carbon dioxide using 1000, G-6.1
permanently installed containers with product capacities
greater than ____lbs, shall comply with CGA ____
Braze joints shall have a temperature rating of no less than 1000 degrees Fahrenheit
____
Memory metal fittings shall have a temperature rating point 1000 degrees Fahrenheit
of no less than ____
Axial swaged fittings shall be able to withstand a 1000 degrees Fahrenheit
temperature of ____
Metallic flexible joint for seismic protection or thermal 1000 degrees Fahrenheit
expansion shall withstand temperatures of ____
Auxiliary connections shall be the same size as the main, 2 inch
but are not required to be larger than ____
Category ____ space: In which failure of equipment or a 2
system is likely to cause minor injury to patients, staff, or
visitors
Category ____ dental: facilities utilizing only moderate and 2
minimal sedation
Medical air supply systems shall have less than ____ of 2 ppm
halogenated hydrocarbons
Master alarm panels shall consists of ____ or more panels two
Liquid containers shall have visible identification with a 2 inch
minimum of letters ____ high
Manifolds for gas cylinders shall have ____ equal headers two
Manifolds header for gas cylinders shall have no fewer two
than ____ connections