NFPA 99 Med Gas TEST FINAL EXAM AND PRACTICE EXAM
20262027 BANK 2 VERSIONS QUESTIONS WITH DETAILED
VERIFIED ANSWERS EXAM QUESTIONS WILL COME
FROM HERE (100% CORRECT ANSWERS A+ GRADED
An existing system that is not in the strict compliance with the
provisions of this code shall be permitted to be continued in use as long
as _______ has determined that such use does not constitute a distinct
hazard to life. - ANSWER--Authority having jurisdiction
Cylinder and cryogenic liquid container outlet connections shall be
designed as to render the attachment point _______ when removal of
the outlet connection is attempted - ANSWER--Unusable
Cylinders in use and in storage shall be prevented from reaching
temperatures in excess of _____ F° - ANSWER--125
Nitrous oxide and carbon dioxide using cylinders or portable containers
shall be prevented from reaching temperatures lower than ______ F° -
ANSWER--20
Which system shall not be permitted to be located in an outdoor
enclosure? - ANSWER--Medical Air Sources
,2|Page
Indoor locations for Oxygen, Nitrous Oxide, and mixtures of these gases
shall not communicate with anything except? - ANSWER--Designated
storage area
Locations for Central supply systems shall have _______ devices
protected from physical damage. - ANSWER--Electrical
Outdoor locations surrounded by impermeable walls, except fire barrier
walls, shall have protected ventilation openings at the _______ of each
wall to allow free circulation of air within the enclosure. - ANSWER--
Base
All positive pressure supply systems shall be provided with duplex line
pressure regulators piped in _______. - ANSWER--Parallel
All pressure relief valves shall be made of brass, bronze or _______. -
ANSWER--Stainless steel
Central supply systems for positive pressure gases shall have one or
more relief valves, the valves shall have a relief setting that is _____%
above normal operating pressure. - ANSWER--50
,3|Page
When vented to the outside, relief valve vent lines shall be labeled in
which way? - ANSWER--Any manner that will distinguish them from the
medical gas pipeline
An auxiliary source connection shall consist of - ANSWER--Visual
pressure indicator
In central supply systems using gas or liquid cylinders, each header shall
have a ______ to prevent debris from entering the manifold controls. -
ANSWER--Filter
Manifolds for gas cylinders shall consist of two equal headers, each
header with enough cylinders for an average days supply, not not fewer
than ______ connections. - ANSWER--2
Manifolds for gas cylinders shall have a _____ signal that visibly
indicates the operating status of the equipment and shall activate an
indicator at all master alarm panels when or just before changeover
from one header to the other takes place. - ANSWER--Local
When multiple buildings are served from a single cryogenic liquid
oxygen source, it is required to place the emergency oxygen supply
connection in ______. - ANSWER--Each building served
The minimum clearance around EOSC for a temporary source of supply
is _______ ft. - ANSWER--3
, 4|Page
An ______ emergency reserve system can be substituted for the EOSC.
- ANSWER--In building
Nitrous oxide cylinders shall be prevented from reaching temperatures
in excess of. - ANSWER--125 degrees F
Carbon dioxide cylinders shall be prevented from reaching
tempertaures below. - ANSWER--20 degrees F
Central supply systems for positive pressure gasses shall have one or
more relief valves with the relief setting above nromal operating
pressure. - ANSWER--50%
Completed Manufactured Assesmblies being tested at 20% above
operating pressure shall not exceedthis percentage for leakage? -
ANSWER--0.5%
Activities , systems , or equipment whose failure is likely to cause major
injury or death of patients, staff, or visitors. - ANSWER--Category 1
Activities, systems, or equipment whose failure is likely to cause minor
injury to patients, staff, or visitors. - ANSWER--Category 2