◉ For use underground, including direct burial in the earth, type
_______ cable is permitted.
340.10. Answer: UF
◉ When type IMC conduit is conduit is treaded in the field, a
standard cutting die with a taper of 1 in 16 _________ per foot shall be
used.
342.28. Answer: 3/4
◉ Type RMC shall be permitted to be installed in or under cinder fill
not less than _________ inches.
344.13(c). Answer: 18
◉ There shall be more than the equivalent of ____________ quarter
bends 360 degrees total between pull point, for example, conduit
bodies and boxes.
344.28. Answer: 4
,◉ The RMC shall be securely fastened within __________ feet of each
outlet box, junction box, device box, and cabinet.
344.30(a). Answer: 3
◉ Running threads __________ used on conduit for connection at
couplings.
344.42(a). Answer: shall not be
◉ Type FMC shall be surely fastened in place by an approved means,
within __________ inches of each box
348.30. Answer: 12
◉ Type RNC shall not be used for the support of ___________ or any
other equipment.
352.11(h). Answer: Luminaries (fixtures)
◉ Type NUCC shall not be used in the following areas _____________.
352.12. Answer: inside building
◉ The maximum size of EMT tubing shall be metric trade size
__________.
358.20. Answer: 4
, ◉ The ENT _________ used where exposed to direct rays of the sun,
unless identified as sunlight resistance.
362.12. Answer: shall not be
◉ An auxiliary gutter shall not extend a greater distance than
__________ beyond the equipment it supplement.
366.12. Answer: 30 ft
◉ Non metallic auxiliary gutters shall have expansion fitting
installed where the expected length change due to expansion and
contraction due to temperature change is more than ________ inches.
366.14. Answer: 0.25
◉ Bus-ways shall be permitted to be _______________ and are visible.
368.10. Answer: open
◉ The length of the suitable coat and cable assemblies approved for
extra hard usage for branches from bus-ways for the connection of
equipment shall not exceed ________ feet.
368.17(b)(7). Answer: 6
◉ Cable-bus shall be permitted to extend vertically through dry floor
and platforms, provided the cable-bus is totally enclose at the point
TELECOMMUNICATIONS CERTIFICATION
EXAMINATION TEST 2026
◉ For use underground, including direct burial in the earth, type
_______ cable is permitted.
340.10. Answer: UF
◉ When type IMC conduit is conduit is treaded in the field, a
standard cutting die with a taper of 1 in 16 _________ per foot shall be
used.
342.28. Answer: 3/4
◉ Type RMC shall be permitted to be installed in or under cinder fill
not less than _________ inches.
344.13(c). Answer: 18
◉ There shall be more than the equivalent of ____________ quarter
bends 360 degrees total between pull point, for example, conduit
bodies and boxes.
344.28. Answer: 4
,◉ The RMC shall be securely fastened within __________ feet of each
outlet box, junction box, device box, and cabinet.
344.30(a). Answer: 3
◉ Running threads __________ used on conduit for connection at
couplings.
344.42(a). Answer: shall not be
◉ Type FMC shall be surely fastened in place by an approved means,
within __________ inches of each box
348.30. Answer: 12
◉ Type RNC shall not be used for the support of ___________ or any
other equipment.
352.11(h). Answer: Luminaries (fixtures)
◉ Type NUCC shall not be used in the following areas _____________.
352.12. Answer: inside building
◉ The maximum size of EMT tubing shall be metric trade size
__________.
358.20. Answer: 4
, ◉ The ENT _________ used where exposed to direct rays of the sun,
unless identified as sunlight resistance.
362.12. Answer: shall not be
◉ An auxiliary gutter shall not extend a greater distance than
__________ beyond the equipment it supplement.
366.12. Answer: 30 ft
◉ Non metallic auxiliary gutters shall have expansion fitting
installed where the expected length change due to expansion and
contraction due to temperature change is more than ________ inches.
366.14. Answer: 0.25
◉ Bus-ways shall be permitted to be _______________ and are visible.
368.10. Answer: open
◉ The length of the suitable coat and cable assemblies approved for
extra hard usage for branches from bus-ways for the connection of
equipment shall not exceed ________ feet.
368.17(b)(7). Answer: 6
◉ Cable-bus shall be permitted to extend vertically through dry floor
and platforms, provided the cable-bus is totally enclose at the point