with Verified Correct Answers | Complete &
Graded A+
96" AFF and a least 6" below the ceiling - ANSWER -what is the appropriate
mounting high for audible notification appliance?
listed - ANSWER -A multi criteria device shall be ____ for the primary function
of the device
15% - ANSWER -Spaces separated by a partition shall be considered as separate
room for projected beam smoke detectors when the partition extend to within what
percentage of the ceiling high?
Soft tissue injuries - ANSWER -which of the following is caused by muscle pains
and spams?
3.19 ohm - ANSWER -what is the wire resistance in ohms, of 1000 feet of 14
AWG solid copper which is coated at 75 degrees C?
200 seconds - ANSWER -a trouble signal shall be indicated and recorded
with____seconds?
Shunt - ANSWER -What type of auxiliary fire alarm system does not permit the
use of automatic detectors?
110 % - ANSWER -A steam pressure supervisory shall indicate a low pressure
condition .The off normal signal be initiated prior to the pressure falling below
_____% of the minimum operating equipment supplied?
7 AMP - ANSWER -A non power limited fire alarm circuit which 18 AWG shall
have over current protection not to exceed ___ amperes?
The system designer - ANSWER -the features for non required system shall be
established by _____ on the basis of the goals and objectives of the building owner
?
, 8.08 ohm - ANSWER -What is the resistance in ohms, of 1000 feet of 18 AWG
solid copper which is coated at 75 degrees C?
Listing - ANSWER -The effect of guards, covers, or lents on the appliances field
performance shall be in accordance with _____requirements?
monthly - ANSWER -What is the testing frequency for household smoke alarm ?
Proprietary Supervisory Station Service - ANSWER -What type of supervising
station fire alarm system is characterized by the bldg .Which are protected and the
supervising station being under the same ownership?
FPLP - ANSWER -which of the following are acceptable cable for use in an
environmental air return space ?
monthly - ANSWER -Consider a household fire alarm system which
communicates to a supervising station .What type is the testing frequency for the
communication path?
2 devices - ANSWER -In corridors where more than _____ visible notification
appliances are in any field of view they ,shall be synchronized.
6 smk det - ANSWER -Consider a room with smooth a flat 10' ceiling which is
60' x 90' .What is the minimum number of smoke detectors required to cover this
space?
Check for breathing - ANSWER -what measures should be taken after
determining the extent of a wounded person injury?
16 feet - ANSWER -Consider the use of visible appliances in sleeping areas.For
rooms with a linear dimension greater than 16 feet, the visible appliance shall be
located within _____feet of the pillow?
18 months - ANSWER -When a device is inaccessible due to excessive height,
such as an atrium, what it the maximum interval for testing?
30 days - ANSWER -supervising station customers shall be notified in writing of
any schedule change in service that results in signals being handled by a different
supervising station. what frame shall this requirement comply within?