6 smk det - ANSWERS-Consider a room with smooth a flat
10' ceiling which is 60' x 90' .What is the minimum number
of smoke detectors required to cover this space?
Check for breathing - ANSWERS-what measures should be
taken after determining the extent of a wounded person
injury?
16 feet - ANSWERS-Consider the use of visible appliances in
sleeping areas.For rooms with a linear dimension greater
than 16 feet, the visible appliance shall be located within
_____feet of the pillow?
,18 months - ANSWERS-When a device is inaccessible due to
excessive height, such as an atrium, what it the maximum
interval for testing?
30 days - ANSWERS-supervising station customers shall be
notified in writing of any schedule change in service that
results in signals being handled by a different supervising
station. what frame shall this requirement comply within?
300 volts - ANSWERS-PLFA cables shall be have a voltage
rating of not less than ____ volts.
Semi-annually - ANSWERS-Waterflow devices shall be tested
with that frequency?
Annually - ANSWERS-With what frequency shall ionization
smoke detectors be given a functional test?
24 hours in normal operation, 5 minutes in alarm -
ANSWERS-What are the standby power requirements for a
proprietary signaling system?
,Shunt type - ANSWERS-Which of the following is a type of
auxiliary protective signaling system?
A UL listed central station
A receiver located at an unlisted monitoring facility
A fire department or communications center - ANSWERS-
Remote station signaling systems are permitted to send
signals to:
600V - ANSWERS-Non-power limited fire alarm cable shall
have an insulation rating of:
4 wires - ANSWERS-what is the maximum number of 14
AWG RHH conductors which can be installed in 1/2 rigid
metal conduit?
3.5'-48" to the actuator - ANSWERS-Which of the following
would be an appropriate mounting height for a pull station?
1 flash per second - ANSWERS-What is the minimum flash
rate for a visible notification device?
, 90" to the top of the device - ANSWERS-What is the
minimum mounting height for audible notification devices?
Such that the entire lens is not less then 80" - ANSWERS-
What is the minimum mounting height for visible
notification devices?
Voltage=Current X Resistence - ANSWERS-What is the
formula for Ohm's Law
Put your meter in series with the circuit - ANSWERS-When
using your mult-meter to measure, you must:
20,000 CFM HVAC system serving a single floor
15,000 CFM HVAC system serving 3 floors
20,000 CFM HVAC system serving 2 floors - ANSWERS-Which
of these HVAC systems would require duct detectors on
supply and return?
Group A, E, F - ANSWERS-According to the IBC, which of the
following use Groups require visual notification?