Minnesota Post Test GRADED A+ GUARANTEED PASS How often do you inspect private fire hydrants? Annually or after each operation Reference: NFPA 25, 2017 Edition, Section 7.3.1 specifies that private fire hydrants shall be inspected annually or after each operation. What is NFPA 13R used for? Residential occupancies up to and including four stories in height Reference: NFPA 13R, 2016 Edition is titled “Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies.” What is the coverage area for Ordinary Hazard heads? 130 square feet Reference: NFPA 13, 2016 Edition, Table 8.6.2.2.1(b) What is the coverage area for Light Hazard heads? 225 square feet Reference: NFPA 13, 2016 Edition, Section 8.6.2.2.1 and Table 8.6.2.2.1(a) and Minnesota State Fire Code, 2020 Edition, Section 903.3.1.1 adopts NFPA 13 by reference. What is the coverage area for Extra Hazard heads? 90-130 square feet 2 | P a g e Reference: NFPA 13, 2016 Edition specifies typical coverage areas for extra hazard occupancies, although specific variations may apply based on the hazard type and storage arrangement. What is the coverage area for ESFR heads? 100 square feet Reference: NFPA 13, 2016 Edition, Section 8.12.2.2.1 specifies the maximum allowable coverage area for ESFR sprinklers. What is the coverage area for Storage heads? 100 or 130 square feet Reference: NFPA 13, 2016 Edition, Section 12.6.2 specifies typical coverage areas for storage occupancies, although specific variations may apply based on commodity classification and storage height. Minimum air pressure for a pressure tank? 75 psi Reference: NFPA 20, 2016 Edition, Section 14.2.4 specifies that the minimum air pressure in a pressure tank shall be 75 psi. What pipe sizes can feed 1½" hose lines and for what length? 1" for horizontal runs up to 20’ 1¼" for 20’ to 80’ 1½" for runs over 80’ Reference: NFPA 14, 2016 Edition, Section 7.3.1 specifies the minimum pipe sizes for 1½" hose lines based on length. What are the bulb colors for each temperature rating? Ordinary (135°F to 170°F / 57°C to 77°C): Glass Bulb Colors: Orange or Red 3 | P a g e Intermediate (175°F to 225°F / 79°C to 107°C): Glass Bulb Colors: Yellow or Green High (250°F to 300°F / 121°C to 149°C): Glass Bulb Colors: Blue Extra High (325°F to 375°F / 163°C to 191°C): Glass Bulb Colors: Purple Reference: NFPA 13, 2016 Edition, Table 5.1.1.6.1 Question 104 Control valves that are controlling a fire sprinkler system in an area accessible to the public, and has 20 or less sprinklers on it does not have to be monitored or locked. True/False False Per Minnesota State Fire Code, 2020 Edition, Section 903.4, all control valves for fire sprinkler systems shall be electrically supervised by a listed fire alarm control unit, regardless of the number of sprinklers served. This requirement does not have an exception for systems with 20 or fewer sprinklers when accessible to the public. Reference: Minnesota State Fire Code, 2020 Edition, Section 903.4 How often is the interior of a pressure tank inspected? The interior of pressure tanks used for fire protection systems must be inspected every 5 years and every 3 years for tanks without corrosion protection. Reference: NFPA 25, 2017 Edition, Section 9.2.5.1.1 specifies that the interior of steel tanks without corrosion protection shall be inspected every 3 years

Meer zien Lees minder
Instelling
Minnesota Post Tes
Vak
Minnesota Post Tes

Voorbeeld van de inhoud

1|Page



Minnesota Post Test GRADED A+ GUARANTEED
PASS

How often do you inspect private fire hydrants?
Annually or after each operation
Reference: NFPA 25, 2017 Edition, Section 7.3.1 specifies that private
fire hydrants shall be inspected annually or after each operation.


What is NFPA 13R used for?
Residential occupancies up to and including four stories in height
Reference: NFPA 13R, 2016 Edition is titled “Standard for the Installation
of Sprinkler Systems in Low-Rise Residential Occupancies.”


What is the coverage area for Ordinary Hazard heads?
130 square feet
Reference: NFPA 13, 2016 Edition, Table 8.6.2.2.1(b)


What is the coverage area for Light Hazard heads?
225 square feet
Reference: NFPA 13, 2016 Edition, Section 8.6.2.2.1 and Table
8.6.2.2.1(a) and Minnesota State Fire Code, 2020 Edition, Section
903.3.1.1 adopts NFPA 13 by reference.


What is the coverage area for Extra Hazard heads?
90-130 square feet

,2|Page


Reference: NFPA 13, 2016 Edition specifies typical coverage areas for
extra hazard occupancies, although specific variations may apply based
on the hazard type and storage arrangement.

What is the coverage area for ESFR heads?
100 square feet
Reference: NFPA 13, 2016 Edition, Section 8.12.2.2.1 specifies the
maximum allowable coverage area for ESFR sprinklers.


What is the coverage area for Storage heads?
100 or 130 square feet
Reference: NFPA 13, 2016 Edition, Section 12.6.2 specifies typical
coverage areas for storage occupancies, although specific variations may
apply based on commodity classification and storage height.

Minimum air pressure for a pressure tank?
75 psi
Reference: NFPA 20, 2016 Edition, Section 14.2.4 specifies that the
minimum air pressure in a pressure tank shall be 75 psi.


What pipe sizes can feed 1½" hose lines and for what length?
1" for horizontal runs up to 20’
1¼" for 20’ to 80’
1½" for runs over 80’
Reference: NFPA 14, 2016 Edition, Section 7.3.1 specifies the minimum
pipe sizes for 1½" hose lines based on length.


What are the bulb colors for each temperature rating?
Ordinary (135°F to 170°F / 57°C to 77°C):
Glass Bulb Colors: Orange or Red

,3|Page


Intermediate (175°F to 225°F / 79°C to 107°C):
Glass Bulb Colors: Yellow or Green
High (250°F to 300°F / 121°C to 149°C):
Glass Bulb Colors: Blue
Extra High (325°F to 375°F / 163°C to 191°C):
Glass Bulb Colors: Purple
Reference:
NFPA 13, 2016 Edition, Table 5.1.1.6.1


Question 104
Control valves that are controlling a fire sprinkler system in an area
accessible to the public, and has 20 or less sprinklers on it does not have
to be monitored or locked.
True/False
False
Per Minnesota State Fire Code, 2020 Edition, Section 903.4, all control
valves for fire sprinkler systems shall be electrically supervised by a listed
fire alarm control unit, regardless of the number of sprinklers served.
This requirement does not have an exception for systems with 20 or
fewer sprinklers when accessible to the public.
Reference:
Minnesota State Fire Code, 2020 Edition, Section 903.4


How often is the interior of a pressure tank inspected?
The interior of pressure tanks used for fire protection systems must be
inspected every 5 years and every 3 years for tanks without corrosion
protection.
Reference:
NFPA 25, 2017 Edition, Section 9.2.5.1.1 specifies that the interior of
steel tanks without corrosion protection shall be inspected every 3
years.

, 4|Page




How often do you flow standpipes?
5 years
Reference: NFPA 25, 2017 Edition, Section 6.3.2.1 specifies that
standpipes shall be flow tested at least every 5 years.


How many heads can be taken off a cold weather valve?
10
Reference: NFPA 13, 2016 Edition, Section 8.16.1.5.3 specifies that up to
10 sprinklers can be taken off a cold weather valve.
Hanger spacing from end of pipe
1" - 3’
1¼" - 4’
1½" and up - 5’
Reference: NFPA 13, 2016 Edition, Section 9.2.3.4.1 specifies the
following hanger spacing from the end of the pipe:
For 1-inch pipe: 36 inches
For 1 1/4-inch pipe: 48 inches
For 1 1/2-inch pipe and larger: 60 inches
Duration of water supply for NFPA 13D systems
System demand times 10 minutes
Reference: NFPA 13D, 2016 Edition, Section 8.6.2 specifies that the
water supply for one- and two-family dwellings should be sufficient for
the system demand for a minimum of 10 minutes.


Why must a check valve with a 3/32" hole in the Clapper be installed in
the system riser below the test valve in freezer spaces?
To prevent evaporation of priming water into system
Reference: NFPA 13, 2016 Edition, Section 7.8.2.7.1 specifies that a
check valve with a small hole in the clapper helps to maintain a slight air

Geschreven voor

Instelling
Minnesota Post Tes
Vak
Minnesota Post Tes

Documentinformatie

Geüpload op
4 december 2024
Aantal pagina's
284
Geschreven in
2024/2025
Type
Tentamen (uitwerkingen)
Bevat
Vragen en antwoorden

Onderwerpen

Maak kennis met de verkoper

Seller avatar
De reputatie van een verkoper is gebaseerd op het aantal documenten dat iemand tegen betaling verkocht heeft en de beoordelingen die voor die items ontvangen zijn. Er zijn drie niveau’s te onderscheiden: brons, zilver en goud. Hoe beter de reputatie, hoe meer de kwaliteit van zijn of haar werk te vertrouwen is.
laurenjames james
Volgen Je moet ingelogd zijn om studenten of vakken te kunnen volgen
Verkocht
88
Lid sinds
2 jaar
Aantal volgers
16
Documenten
1519
Laatst verkocht
4 weken geleden
LaurenJames

Welcome to My Stuvia Page! I'm, a dedicated medical doctor (MD) with a passion for helping students excel in their exams. With my extensive experience in the medical field, I provide comprehensive support and effective study techniques to ensure academic success. My unique approach combines medical knowledge with practical strategies, making me an invaluable resource for students aiming for top performance. Discover my proven methods and start your journey to academic excellence with me on Stuvia today! Hi there! I'm Lauren James, and I'm here to provide high-quality study materials to help you succeed. With a focus on clarity and usefulness, my notes are designed to make your studying easier and more efficient. If you ever need assistance or have any questions, feel free to reach out. Let's achieve your academic goals together! Contact me via MESSAGE for any assisstance. Good luck! Simple well-researched education material for you. Please rate my work and write a review GOOD LUCK IN YOUR EXAM! Feel free to tweak it based on your style!

Lees meer Lees minder
3,6

12 beoordelingen

5
5
4
2
3
2
2
1
1
2

Populaire documenten

Recent door jou bekeken

Waarom studenten kiezen voor Stuvia

Gemaakt door medestudenten, geverifieerd door reviews

Kwaliteit die je kunt vertrouwen: geschreven door studenten die slaagden en beoordeeld door anderen die dit document gebruikten.

Niet tevreden? Kies een ander document

Geen zorgen! Je kunt voor hetzelfde geld direct een ander document kiezen dat beter past bij wat je zoekt.

Betaal zoals je wilt, start meteen met leren

Geen abonnement, geen verplichtingen. Betaal zoals je gewend bent via iDeal of creditcard en download je PDF-document meteen.

Student with book image

“Gekocht, gedownload en geslaagd. Zo makkelijk kan het dus zijn.”

Alisha Student

Veelgestelde vragen