Insulated conductors of No. 6 or smaller intended for use as grounded conductors in a circuit
must be either of the following colors: NEC Section 200.6(A. and 200.6(B.. - CORRECT ANSWER-
White, gray or have three continuous white or gray stripes on other than green insulation
Direct buried conductors and cables emerging from grade shall be protected by an enclosure or
raceway a distance above ground of no less than: NEC Section 300.5(D)(1). - CORRECT ANSWER-
8 feet
Cable tray systems must not be used: NEC Section 392.12. - CORRECT ANSWER- in hoistways
A 15- or 20-ampere laundry circuit is required in each: NEC Section 210.52(F). - CORRECT
ANSWER- dwelling unit
Holes in wood studs for cables must be drilled in the center of the stud and a distance from the
nearest edge of not less than: NEC Section 300.4(A.(1) - CORRECT ANSWER- 1 1/4 inches
When a branch circuit feeds both non continuous and continuous loads, the circuit must be
sized to accommodate 100% of the noncontinuous load plus what percent of the continuous
load? NEC Section 210.20(A) - CORRECT ANSWER- 125%