BICSI TECHNICIAN EXAM
Study online at https://quizlet.com/_i1eatm
1. L Rating: A firestops ability to provide a smoke stop. (air leakage rate)
2. To avoid damaging cable jacket, how often must you securely fasten electrical
nonmetallic tubing (ENT): 3 Feet so it does not damage the cable
3. What is the minimum dedicated power requirement of a telecommunications
enclosure: 120 V ac/20
4. The clearance behind the PBB when mounted, should be no less than-: 2inch
clearance behind the PBB when mounted
5. When installing a plywood backboard, you should use galvanized screws that
are a minimum of ______ longer than the depth of the wall covering, including
the plywood: 0.5in
6. The use of under carpet telecommunications cable should be limited to:: The
interconnection point between horizontal cabling and UTC is a transition point (TP)
7. Two 90-degree bends are allowed in any one conduit segment. A third bend
may be acceptable under certain situations: Runs under 33 feet
8. When installing racks and cabinets on an access floor, what should they be
secured to?: The frame
9. When placing cabinets on an access floor, how should the cabinets be
aligned?: One edge flush with the floor tile cut line
10. What is a telecommunications enclosure TE used for?: May be used to provide a suitable
option for moves, adds, and changes without compromising infection control measures and other restrictions
11. What size threaded rod would you typically use in a heavy duty ladder rack
installation?: 5/8in
12. A supplemental bonding network within an ER or data center consisting of a
set of conductors formed into a grid is often associated with what?: Access flooring
13. Which type of anchor requires a hole to be drilled into the floor where the
attachment is to be made?: Expansion anchors
14. Min seperation from electric motors and transformers?: 48"
15. During which phase of the project would you determine cable labeling
requirements?: Pre-construction Phase
16. What type of documentation uses the original floor plans and reflects the ac-
tual installed outlet locations, cables, length, and firestopping materials?: Record
drawings
1/4
Study online at https://quizlet.com/_i1eatm
1. L Rating: A firestops ability to provide a smoke stop. (air leakage rate)
2. To avoid damaging cable jacket, how often must you securely fasten electrical
nonmetallic tubing (ENT): 3 Feet so it does not damage the cable
3. What is the minimum dedicated power requirement of a telecommunications
enclosure: 120 V ac/20
4. The clearance behind the PBB when mounted, should be no less than-: 2inch
clearance behind the PBB when mounted
5. When installing a plywood backboard, you should use galvanized screws that
are a minimum of ______ longer than the depth of the wall covering, including
the plywood: 0.5in
6. The use of under carpet telecommunications cable should be limited to:: The
interconnection point between horizontal cabling and UTC is a transition point (TP)
7. Two 90-degree bends are allowed in any one conduit segment. A third bend
may be acceptable under certain situations: Runs under 33 feet
8. When installing racks and cabinets on an access floor, what should they be
secured to?: The frame
9. When placing cabinets on an access floor, how should the cabinets be
aligned?: One edge flush with the floor tile cut line
10. What is a telecommunications enclosure TE used for?: May be used to provide a suitable
option for moves, adds, and changes without compromising infection control measures and other restrictions
11. What size threaded rod would you typically use in a heavy duty ladder rack
installation?: 5/8in
12. A supplemental bonding network within an ER or data center consisting of a
set of conductors formed into a grid is often associated with what?: Access flooring
13. Which type of anchor requires a hole to be drilled into the floor where the
attachment is to be made?: Expansion anchors
14. Min seperation from electric motors and transformers?: 48"
15. During which phase of the project would you determine cable labeling
requirements?: Pre-construction Phase
16. What type of documentation uses the original floor plans and reflects the ac-
tual installed outlet locations, cables, length, and firestopping materials?: Record
drawings