P-13 BULK OIL STORAGE FACILITY Questions with
Detailed Verified Answers
HOT WORK AUTHORIZATIONS ARE TO BE ISSUED ____________. Ans: ✓ ✓ ✓ DAILY
HOT WORK PERMITS ARE ISSUED BY THE __________, THEY ARE DIFFERENT FROM HOT WORK
AUTHORIZATIONS. Ans: ✓ ✓ ✓ FDNY
A ____________ SHALL BE CONDUCTED BY THE RESPONSIBLE PERSON PRIOR TO WORK TO ENSURE
THAT ALL EQUIPMENT IS SAFE. Ans: ✓ ✓ ✓ PRE-HOT WORK CHECK
TRANSFERRING TANK TO LOADING RACK REQUIRES ________ COF HOLDER. Ans: ✓ ✓ ✓ ONE
WHEN A FIRE PROTECTION SYS. IS OUT OF SERVICE, THE COF HOLDER MUST NOTIFY ____________.
Ans: ✓ ✓ ✓ MANAGEMENT
THE P-13 COF HOLDER MUST ENSURE THAT TRUCKS ENTERING HAVE A VALID _____________. Ans:
✓ ✓ ✓ FDNY PERMIT
THE ____________ IS RESPONSIBLE FOR MAKING SURE THAT ALL FIRE SAFETY REGULATIONS AND
PROCEDURES ARE OBEYED ON THE PREMISES. Ans: ✓ ✓ ✓ COF HOLDER
ALL RECORDS SHOULD BE KEPT FOR AT LEAST ___________ YEARS. Ans: ✓ ✓ ✓ 5
DEPENDING ON THE PRODUCT SERVICE, INTERIOR OF TANKS SHALL BE INSPECTED EVERY
____________ YEARS. Ans: ✓ ✓ ✓ 10
___________ TANKS MAY BE USED TO STORE PRODUCTS WITH HIGH FLASH POINTS. Ans: ✓ ✓ ✓
CONE ROOF
A __________ SYSTEM MAY BE INSTALLED WHEN A CONE ROOF IS USED TO STORE PRODUCTS
WITH A LOW FLASH POINT. Ans: ✓ ✓ ✓ VAPOR RECOVERY SYSTEM
THE VAPOR RECOVERY UNITS MUST BE INSPECTED AT LEAST ONCE EVERY ___________ MONTHS.
Ans: ✓ ✓ ✓ 6
© Get it right 2025 Getaway - Stuvia US All rights reserved
, Click here for more: Scholars nexus
THERE ARE TWO TYPES OF FLOATING ROOF TANKS: __________ AND ___________. Ans: ✓ ✓ ✓
OPEN-TOP AND COVERED TOP
VENTS FOR FLOATING ROOF TANKS ARE LOCATED BETWEEN THE ________________. Ans: ✓ ✓ ✓
FLOATING ROOF AND ACTUAL ROOF
MAX HEIGHT OF AN ABOVEGROUND FLAMMABLE AND COMBUSTIBLE TANK SHALL NOT EXCEED
____________ FEET. Ans: ✓ ✓ ✓ 40
ABOVEGROUND VERTICAL CYLINDRICAL TANKS STORING COMBUSTIBLE LIQUIDS SHALL NOT
EXCEED ______________ FEET. Ans: ✓ ✓ ✓ 48
ANYTIME A TANK IS ALTERED OR REPAIRED, IT IS SUBJECT TO A ____________ STANDING WATER
TEST. Ans: ✓ ✓ ✓ 24 HOUR
VARECS SHALL BE TESTED ________ FOR ACCURACY AND FREEDOM OF MOVEMENT. Ans: ✓ ✓ ✓
EVERY YEAR
TANK FIELDS MUST BE INSPECTED DAILY FOR COMBUSTIBLE TRASH, ACCUMULATION OF
CORROSION, AND ___________ BUILDUP. Ans: ✓ ✓ ✓ ICE
THE HIGH ALARMS SHALL BE CONNECTED TO THE _____________ OFFICE. Ans: ✓ ✓ ✓
DISPATCHER'S
TANKS FILLED BY ANY PIPELINE SHALL BE PROVIDED WITH A __________ VALVE. Ans: ✓ ✓ ✓
BRODIE
THE "HI" ALARM SHOULD BE CALIBRATED TO A FILL LEVEL OF ___________ PERCENT. Ans: ✓ ✓ ✓
95
THE "HI-HI" ALARM SHOULD BE CALIBRATED TO A FILL LEVEL OF __________ PERCENT. Ans: ✓ ✓ ✓
98
EACH SINGLE DIKE WALL ENCLOSURE SHALL HAVE A CAPACITY EQUAL TO _________ PERCENT OF
THE TANK'S CAPACITY. Ans: ✓ ✓ ✓ 110
TANKS ARRANGED IN GROUPS WITH A TOTAL CAPACITY NOT EXCEEDING ___________ GALLONS
MAY BE ENCLOSED IN A SINGLE DIKE ENCLOSURE. Ans: ✓ ✓ ✓ 500,000
INTERMEDIATE DIKES SHALL NOT BE LESS THAN _________ INCHES IN HEIGHT. Ans: ✓ ✓ ✓ 18
© Get it right 2025 Getaway - Stuvia US All rights reserved
P-13 BULK OIL STORAGE FACILITY Questions with
Detailed Verified Answers
HOT WORK AUTHORIZATIONS ARE TO BE ISSUED ____________. Ans: ✓ ✓ ✓ DAILY
HOT WORK PERMITS ARE ISSUED BY THE __________, THEY ARE DIFFERENT FROM HOT WORK
AUTHORIZATIONS. Ans: ✓ ✓ ✓ FDNY
A ____________ SHALL BE CONDUCTED BY THE RESPONSIBLE PERSON PRIOR TO WORK TO ENSURE
THAT ALL EQUIPMENT IS SAFE. Ans: ✓ ✓ ✓ PRE-HOT WORK CHECK
TRANSFERRING TANK TO LOADING RACK REQUIRES ________ COF HOLDER. Ans: ✓ ✓ ✓ ONE
WHEN A FIRE PROTECTION SYS. IS OUT OF SERVICE, THE COF HOLDER MUST NOTIFY ____________.
Ans: ✓ ✓ ✓ MANAGEMENT
THE P-13 COF HOLDER MUST ENSURE THAT TRUCKS ENTERING HAVE A VALID _____________. Ans:
✓ ✓ ✓ FDNY PERMIT
THE ____________ IS RESPONSIBLE FOR MAKING SURE THAT ALL FIRE SAFETY REGULATIONS AND
PROCEDURES ARE OBEYED ON THE PREMISES. Ans: ✓ ✓ ✓ COF HOLDER
ALL RECORDS SHOULD BE KEPT FOR AT LEAST ___________ YEARS. Ans: ✓ ✓ ✓ 5
DEPENDING ON THE PRODUCT SERVICE, INTERIOR OF TANKS SHALL BE INSPECTED EVERY
____________ YEARS. Ans: ✓ ✓ ✓ 10
___________ TANKS MAY BE USED TO STORE PRODUCTS WITH HIGH FLASH POINTS. Ans: ✓ ✓ ✓
CONE ROOF
A __________ SYSTEM MAY BE INSTALLED WHEN A CONE ROOF IS USED TO STORE PRODUCTS
WITH A LOW FLASH POINT. Ans: ✓ ✓ ✓ VAPOR RECOVERY SYSTEM
THE VAPOR RECOVERY UNITS MUST BE INSPECTED AT LEAST ONCE EVERY ___________ MONTHS.
Ans: ✓ ✓ ✓ 6
© Get it right 2025 Getaway - Stuvia US All rights reserved
, Click here for more: Scholars nexus
THERE ARE TWO TYPES OF FLOATING ROOF TANKS: __________ AND ___________. Ans: ✓ ✓ ✓
OPEN-TOP AND COVERED TOP
VENTS FOR FLOATING ROOF TANKS ARE LOCATED BETWEEN THE ________________. Ans: ✓ ✓ ✓
FLOATING ROOF AND ACTUAL ROOF
MAX HEIGHT OF AN ABOVEGROUND FLAMMABLE AND COMBUSTIBLE TANK SHALL NOT EXCEED
____________ FEET. Ans: ✓ ✓ ✓ 40
ABOVEGROUND VERTICAL CYLINDRICAL TANKS STORING COMBUSTIBLE LIQUIDS SHALL NOT
EXCEED ______________ FEET. Ans: ✓ ✓ ✓ 48
ANYTIME A TANK IS ALTERED OR REPAIRED, IT IS SUBJECT TO A ____________ STANDING WATER
TEST. Ans: ✓ ✓ ✓ 24 HOUR
VARECS SHALL BE TESTED ________ FOR ACCURACY AND FREEDOM OF MOVEMENT. Ans: ✓ ✓ ✓
EVERY YEAR
TANK FIELDS MUST BE INSPECTED DAILY FOR COMBUSTIBLE TRASH, ACCUMULATION OF
CORROSION, AND ___________ BUILDUP. Ans: ✓ ✓ ✓ ICE
THE HIGH ALARMS SHALL BE CONNECTED TO THE _____________ OFFICE. Ans: ✓ ✓ ✓
DISPATCHER'S
TANKS FILLED BY ANY PIPELINE SHALL BE PROVIDED WITH A __________ VALVE. Ans: ✓ ✓ ✓
BRODIE
THE "HI" ALARM SHOULD BE CALIBRATED TO A FILL LEVEL OF ___________ PERCENT. Ans: ✓ ✓ ✓
95
THE "HI-HI" ALARM SHOULD BE CALIBRATED TO A FILL LEVEL OF __________ PERCENT. Ans: ✓ ✓ ✓
98
EACH SINGLE DIKE WALL ENCLOSURE SHALL HAVE A CAPACITY EQUAL TO _________ PERCENT OF
THE TANK'S CAPACITY. Ans: ✓ ✓ ✓ 110
TANKS ARRANGED IN GROUPS WITH A TOTAL CAPACITY NOT EXCEEDING ___________ GALLONS
MAY BE ENCLOSED IN A SINGLE DIKE ENCLOSURE. Ans: ✓ ✓ ✓ 500,000
INTERMEDIATE DIKES SHALL NOT BE LESS THAN _________ INCHES IN HEIGHT. Ans: ✓ ✓ ✓ 18