Refrigeration Excellence Exam A+ Pass Verified 2025 New Update 1. In a dry type (direct expansion) evaporator, liquid refrigerant must boil away as close to the end of the coil as possible in order to: A. Operate at high-efficiency B. Ensure that Frost is not accumulate C. Subcool the compressor D. Ensure proper oil return - Answer- A. Operate at high-efficiency 2. The difference between the temperature of the refrigerant boiling in the evaporator and the temperature at the evaporator outlet is known as A. Evaporator superheat B. Latent heat C. Evaporator sub-cooling D. Sublimation - Answer- A. Evaporator superheat 3. An expansion device that is stuck open will cause A. Low suction pressure B. A starved evaporator C. Excessive superheat D. A flooded evaporator - Answer- D. A flooded evaporator 4. When measuring evaporator superheat on a commercial system that has a long suction line, the pressure reading should be taken at the A. Compressor inlet B. Evaporator outlet C. Condenser outlet D. Receiver Inlet - Answer- A. Compressor inlet 5. Superheat measurements are best taken A. During a hot pulldown B. At 8°F two 12°F C. During defrost D. With the system operating at design conditions - Answer- D. With the system operating at design conditions 6. A technician is checking the superheat on a multi circuit evaporator and finds one of the circuits has a superheat that is higher than the others. This could be caused by A. A dirty coil B. A refrigerant overcharge C. Uneven air distribution D. A blocked distributor - Answer- D. A blocked distributor 7. A TXV with an external equalizer is used on A. Evaporators with a high pressure drop B. Evaporators with a low pressure drop C. High temperature application is only D. All evaporators - Answer- A. Evaporators with a high pressure drop 8. Dry type evaporators operate most efficiently with the superheat setting of approximately A. 8°F to 12°F B. 13°F to 19°F C. 20°F to 30°F D. 31°F to 40°F - Answer- A. 8°F to 12°F 9. An evaporator used to chill liquids is operating within normal superheat setting. But the system is not cooling the product properly. Which of the following is most likely the cause? A. Overcharge of refrigerant B. Undercharge of refrigerant C. The circulator D. The TXV - Answer- A. Overcharge of refrigerant 10. What time interval is required between each superheat adjustment? A. Not less than one hour B. About 10 to 15 minutes C. At least a half hour D. No time delay - Answer- B. About 10 to 15 minutes 11. A low temperature evaporator used for cooling space or product refrigeration A. Is the same as one used for medium or high temperatures B. Must have fins space closer together C. Must be frosted periodically D. Must be defrosted periodically - Answer- D. Must be defrosted periodically 12. Some special applications use a flooded evaporator (operated full of refrigerant) in order to maintain the proper level of liquid refrigerant, a ______ type devices used. A. High side float B. Capillary tube C. AEV D. Low side float - Answer- D. Low side float 13. A properly functioning condenser will first A. Condense, then de-superheat B. Sub-cool, then de-superheat C. Sub-cool, then superheat D. De-superheat, then sub-cool - Answer- D. De-superheat, then sub-cool 14. The effect of an inefficient water cooled condenser will A. Act the same as an air cooled condenser B. Act different than an air cooled condenser C. Always be mixed with incoming medium without being reheated D. Seldom be inefficient on commercial equipment - Answer- A. Act the same as an air cooled condenser 15. The refrigerant condensing temperature in a water cooled condenser is normally about _____ higher than the leaving water. A. 5°F B. 10°F C. 15°F D. 20°F - Answer- B. 10°F 16. The refrigerant and an air cooled condenser will normally contends at approximately _____ higher temperature than the air passing over it. A. 10°F B. 30°F C. 75°F D. 100°F - Answer- B. 30°F 17. Workable head pressure during periods of low ambient temperature can be achieved by using A. An economizer B. Evaporator dampers C. Evaporator flooding D. Fan cycle control - Answer- D. Fan cycle control 18. Cooling towers that pass air over water to remove system heat are limited in capacity by A. Outside air wetbulb temperature B. Outside air dry bulb temperature C. Inside air wetbulb temperature D. Inside air dry bulb temperature - Answer- A. Outside air wetbulb temperature

Vista previa del contenido

Refrigeration Excellence Exam A+
Pass Verified 2025 New Update
1. In a dry type (direct expansion) evaporator, liquid refrigerant must boil away as close
to the end of the coil as possible in order to:
A. Operate at high-efficiency
B. Ensure that Frost is not accumulate
C. Subcool the compressor
D. Ensure proper oil return - Answer- A. Operate at high-efficiency

2. The difference between the temperature of the refrigerant boiling in the evaporator
and the temperature at the evaporator outlet is known as
A. Evaporator superheat
B. Latent heat
C. Evaporator sub-cooling
D. Sublimation - Answer- A. Evaporator superheat

3. An expansion device that is stuck open will cause
A. Low suction pressure
B. A starved evaporator
C. Excessive superheat
D. A flooded evaporator - Answer- D. A flooded evaporator

4. When measuring evaporator superheat on a commercial system that has a long
suction line, the pressure reading should be taken at the
A. Compressor inlet
B. Evaporator outlet
C. Condenser outlet
D. Receiver Inlet - Answer- A. Compressor inlet

5. Superheat measurements are best taken
A. During a hot pulldown
B. At 8°F two 12°F
C. During defrost
D. With the system operating at design conditions - Answer- D. With the system
operating at design conditions

6. A technician is checking the superheat on a multi circuit evaporator and finds one of
the circuits has a superheat that is higher than the others. This could be caused by
A. A dirty coil
B. A refrigerant overcharge
C. Uneven air distribution
D. A blocked distributor - Answer- D. A blocked distributor

,7. A TXV with an external equalizer is used on
A. Evaporators with a high pressure drop
B. Evaporators with a low pressure drop
C. High temperature application is only
D. All evaporators - Answer- A. Evaporators with a high pressure drop

8. Dry type evaporators operate most efficiently with the superheat setting of
approximately
A. 8°F to 12°F
B. 13°F to 19°F
C. 20°F to 30°F
D. 31°F to 40°F - Answer- A. 8°F to 12°F

9. An evaporator used to chill liquids is operating within normal superheat setting. But
the system is not cooling the product properly. Which of the following is most likely the
cause?
A. Overcharge of refrigerant
B. Undercharge of refrigerant
C. The circulator
D. The TXV - Answer- A. Overcharge of refrigerant

10. What time interval is required between each superheat adjustment?
A. Not less than one hour
B. About 10 to 15 minutes
C. At least a half hour
D. No time delay - Answer- B. About 10 to 15 minutes

11. A low temperature evaporator used for cooling space or product refrigeration
A. Is the same as one used for medium or high temperatures
B. Must have fins space closer together
C. Must be frosted periodically
D. Must be defrosted periodically - Answer- D. Must be defrosted periodically

12. Some special applications use a flooded evaporator (operated full of refrigerant) in
order to maintain the proper level of liquid refrigerant, a ______ type devices used.
A. High side float
B. Capillary tube
C. AEV
D. Low side float - Answer- D. Low side float

13. A properly functioning condenser will first
A. Condense, then de-superheat
B. Sub-cool, then de-superheat
C. Sub-cool, then superheat
D. De-superheat, then sub-cool - Answer- D. De-superheat, then sub-cool

, 14. The effect of an inefficient water cooled condenser will
A. Act the same as an air cooled condenser
B. Act different than an air cooled condenser
C. Always be mixed with incoming medium without being reheated
D. Seldom be inefficient on commercial equipment - Answer- A. Act the same as an air
cooled condenser

15. The refrigerant condensing temperature in a water cooled condenser is normally
about _____ higher than the leaving water.
A. 5°F
B. 10°F
C. 15°F
D. 20°F - Answer- B. 10°F

16. The refrigerant and an air cooled condenser will normally contends at approximately
_____ higher temperature than the air passing over it.
A. 10°F
B. 30°F
C. 75°F
D. 100°F - Answer- B. 30°F

17. Workable head pressure during periods of low ambient temperature can be
achieved by using
A. An economizer
B. Evaporator dampers
C. Evaporator flooding
D. Fan cycle control - Answer- D. Fan cycle control

18. Cooling towers that pass air over water to remove system heat are limited in
capacity by
A. Outside air wetbulb temperature
B. Outside air dry bulb temperature
C. Inside air wetbulb temperature
D. Inside air dry bulb temperature - Answer- A. Outside air wetbulb temperature

19. Parallel compressors often referred to as a rack system may use
A. A common suction, but not a common discharge header
B. A common discharge header, but not a comment section header
C. Both comment section header and common discharge header
D. A common accumulator, but never a common receiver - Answer- A. A common
suction, but not a common discharge header

20. The major difference between a cooling tower and an evaporative condenser is
A. Location based on prevailing winds in the angle of the sun
B. The only real difference is design and operating controls of the water flow
C. The refrigerant is cool directly in a cooling tower

Información del documento

Subido en
24 de septiembre de 2025
Número de páginas
16
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$13.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
ScholarExams
3.8
(73)
Vendido
394
Seguidores
186
Artículos
11435
Última venta
4 días hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes