EPA 608 Type 3 Exam with Accurate
Solutions

On low pressure chillers, moisture typically enters the refrigerant system through - ANS-
air leaks from areas with gaskets or fittings

The maximum test pressure for leak testing a low pressure centrifugal is: - ANS-10 psig

Leak test and repair the chiller to reduce refrigerant loss from a pruge unit on CFC-11
chiller - ANS-...

A hydrostatic tube test kit is used to: - ANS-determine if a tube leaks

Commercial and industrial process refrigeration systems must be repaired when the
leak rate exceeds ____ of the charge per year. - ANS-35%

Refrigerant recovery typically start with liquid recovery it is faster. - ANS-...

A rupture disc on a recovery vessel for a low pressure refrigerants relieves at: - ANS-15
psig

According to ASHRAE Guideline 3-1996, if the pressure in a system rises from 1 mm
Hg to a level above ____ during a standing vacuum test, the system should be checked
for leaks. - ANS-2.5 mm Hg

The primary water source for a recovery unit condensing coil is _____. - ANS-local
municipal water supply

When recharging a refrigeration system with R-11, what vaporpressure is necessary in
the shells before changing with liquid? - ANS-16.9" Hg vacuum

After recovering the liquid refrigerant you must: - ANS-recover the vapor refrigerant

According to the EPA there is approximately _____ refrigerant vapor left in an average
350 ton R-11 chiller at 0 psig pressure once all the R-11 liquid has been removed. -
ANS-100 pounds

Charging refrigerant liquid into a refrigeration system when it is under a 29 inch Hg
vacuum can cause the: - ANS-system water to freeze

, A system does not have to be evacuated all the way to the required level when: - ANS-
leaks in the appliance make evacuation to the prescribed level unattainable

Which of the foloowing repairs would ALWAYS be considered "major" under EPA's -
ANS-replacement of evaporator coil

Under EPA's regulation's _______ is used to pressurize a low pressure chiller for the
purpose of opening the system for a non major repair? - ANS-warming the refrigerant

If you are using a recovery machine manufactored AFTER 11-15-93 you must evacuate
an low pressure appliance to _______ before making a major repair. - ANS-25 mm of
Hg absolute

After reaching the required recovery vacuum on a chiller, you should - ANS-Wait for at
least a few minutes to see if the system pressure rises, indicating that there is till
refrigerant in a liquid form or in the oil

The pressure corresponding to 32 F for R-123 - ANS-20 inches of HG vacuum

When evacuating a system the use of too large a vacuum pump can cause? - ANS-
trapped water to freeze

Refrigerant-11 at a pressure of 17 inches HG vacuum has a saturation temperature of: -
ANS-35F

During the evacuation of a system containing large amounts of moisture you can
prevent freezing of this moisture by increasing the pressure with______gas - ANS-
nitrogen

ASHRAE standard 15-1994 requires that each machinery room must activate an alarm
and mechanical ventilation beofre refrigerant concentrations exceed: - ANS-the
threshold limit valve and time weighted average

The typical design burst pressure for a rupture disk on a low pressure centrifugal air-
conditioning system is set at_______ - ANS-15 psi

Heat pumps that have been retrofitted from R22 to R407C should be leak checked with:
- ANS-pressurized nitrogen

When a new system has been assembled, the first thing to do is: - ANS-pressurize the
system with inert gas and leak check

EPA regulations require that leaking commercial or industrial process refrigeration
equipment must be repaired when the leak rate exceeds______ of the charge per year.
- ANS-35%

Información del documento

Subido en
25 de abril de 2025
Número de páginas
10
Escrito en
2024/2025
Tipo
Examen
Contiene
Preguntas y respuestas
$13.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
EXAMHAVEN
5.0
(1)
Vendido
8
Seguidores
2
Artículos
2005
Última venta
3 semanas hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes