Study Guide Test.
An air conditioning service call is made and the complaint is that the system does not seem to be cooling
properly. It is noticed that the suction line and the evaporator coil are frosted up. The filter is checked
and it is clean. It is suspected that the indoor blower is not operating at the proper speed. Technician A
says that the speed can be verified with a strobe tachometer to be sure that the rpms are as written on
the nameplate. Technician B says that the airflow can be measured by taking a static pressure reading.
Which technician is correct? - CORRECT ANSWER technician A
An airflow measurement taken in a duct system by drilling small holes in a vertical and horizontal section
of a rectangular duct to find an average air velocity reading is known as: - CORRECT ANSWER a Pitot-
tube traverse
To calculate velocity pressure when using a manometer, which of the following would be the proper
formula: - CORRECT ANSWER total pressure-static pressure= velocity pressure
What is the primary purpose of an isolation collar: - CORRECT ANSWER It is used to eliminate furnace
vibration through the duct system
During the cooling season, a complaint is made that a two-story home is too cool on the first floor and
too warm on the second floor. What can be done to help the system cool properly: - CORRECT ANSWER
The first-floor in-line dampers can be adjusted perpendicular to the duct
When installing sections of ducts such as plenums, trunk sections, and duct transitions, it is important
to: - CORRECT ANSWER connect the duct sections using the proper S-slips and drive cleats tightly to
prevent duct vibration
A service call is made stating that a family's furnace and duct system has recently been installed by a
friend of the family. The problem is that there doesn't seem to be enough airflow out of the registers.
After arriving to the job, the technician notices that the furnace is 75,000 Btu/h and the air conditioning
system is 2 tons of cooling. After further investigation, the technician notices that the main supply duct
system is 60" by 8" by 25' long. What is the problem with the system: - CORRECT ANSWER The system's
static pressure is too low+The system's main duct is too large