3/8 to ½ inch of the end of the thermocouple - CORRECT ANSWER Should be enveloped by the pilot
flame
A control string is defined as two or more switch contacts connected in a circuit, or set of circuits, to
control a load. In order to troubleshoot a load controlled by a control string, the technician must first: -
CORRECT ANSWER Check for proper voltage applied across the load.
A customer complains the unit is "blowing cold air". The technician determines that the problem occurs
at the end of the heating sequence. The furnace used an electronic integrated blower control. -
CORRECT ANSWER The likely problem with the system is the blower off delay is set too long.
A customer has concerns about carbon monoxide (CO) in their hone. Many of their reported symptoms
indicate there may indeed be a CO problem but on each trip the technician makes to check their home
the technician finds normal CO levels. - CORRECT ANSWER CO detector reader/recorder would be
appropriate to use for determining if a problem truly exists.
A damaged section of double wall vent pipe is to be replaced with a section produced by a different
manufacturer: - CORRECT ANSWER The installer should check the new section for compatible locking
joints.
A dirty or clogged air filter in an operating gas furnace can cause an: - CORRECT ANSWER Increase
temperature rise.
A furnace is inoperative because of a failure in the ignition sequence at the flame proving stage. To
check the flame proving circuit the technician would: - CORRECT ANSWER Connect a microampmeter
set to DC microamps in the sensor circuit and operate the furnace.
A gas clothes dryer can interfere with the operation of a nearby natural draft gas furnace with an
atmospheric burner by: - CORRECT ANSWER Stealing combustion air preventing complete fuel burning.
, A gas furnace should reach a steady state - CORRECT ANSWER Before taking a combustion test
A gas furnace with a standing pilot uses a flame switch for proving pilot flame. - CORRECT ANSWER
Several millivolts are generated by the flame.
A line voltage fuse is sized to protect from: - CORRECT ANSWER Excessive voltage
A meter reading microfarads is used to: - CORRECT ANSWER Check a run capacitor with a capacitance
tester.
A packaged unit in a two story installation is to be located at ground level with ductwork running up the
outside wall to a chase in the second floor. - CORRECT ANSWER The precautions need to be taken with
outside ductwork is it must be insulated and weatherproofed.
A standing pilot furnace uses a relay for controlling the supply blower. On a call for heat, the burner
lights, the fan control closes, but the blower does not run. A check of voltage at the blower relay coil
shows 24V. The load side measures 0V. The technician should replace what: - CORRECT ANSWER Fan
relay.
A system airflow check determines that supply static is 0.15 in. W.C. and return static is a negative 0.55
in. W.C. these readings tell the technician: - CORRECT ANSWER The difference between supply static
and return static is unacceptably low.
A system that is oversized for the load: - CORRECT ANSWER Will cause the unit to short cycle.
A technician is installing a gas furnace and the customer has decided not to install an air conditioner.
Making this decision, the affect it will have on the installation of the supply ductwork is: - CORRECT
ANSWER Leave adequate space should be allowed for addition of a coil in the future when feasible.
A technician measures the return air temperature of a 100,000 BTU output gas furnace to be 65°F and
the supply side air temperature is 135°F: - CORRECT ANSWER The CFM would be 1323.