S 12 CITYWIDE SPRINKLER SYSTEMS EXAM 2025 |
ALL QUESTIONS AND CORRECT ANSWERS (ALREADY
GRADED A+) | VERIFIED ANSWERS | LATEST EXAM
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - (answers)OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES
FOR A MIN. OF __________ YEARS. - (answers)3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - (answers)IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - (answers)1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - (answers)1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO
SERVICE WITHIN ______ HOURS. - (answers)8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. -
(answers)OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________
DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - (answers)30
WHAT DOES "OOS" STAND FOR? - (answers)OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER -
(answers)TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND
ANY SECTIONAL VALVES. - (answers)MASTER FIRE SUPPRESSION PIPING
,2|Page
CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER. - (answers)DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - (answers)NO IMPAIRMENT WAS
FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - (answers)MAIN CONTROL
VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG
PLACED ON THE MAIN CONTROL VALVE. - (answers)RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - (answers)WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - (answers)BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. - (answers)INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - (answers)IMPAIRMENT
COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER
THAN ________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. -
(answers)50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
____________. - (answers)MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE
DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - (answers)RECORDS
, 3|Page
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. - (answers)REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD
THE FOLLOWING CERTS: - (answers)REFRIGERATION OPERATING ENGINEER, HIGH
PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING
ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS. - (answers)MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES
WITH _________ SPRINKLER HEADS OR LESS. - (answers)30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN
SPRINKLERS ARE INSTALLED. - (answers)96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO PREVENT
THE SYSTEM FROM FREEZING. - (answers)40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. -
(answers)COLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - (answers)DRY PIPE
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. -
(answers)AIR PRESSURE
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE ALARM IS
TRANSMITTED DIRECTLY TO THE _________. - (answers)FIRE DEPARTMENT
DRY PIPE VALVES ARE OF A ______ DESIGN. - (answers)CLAPPER
DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL TRIP
LEVEL. - (answers)15-20
S 12 CITYWIDE SPRINKLER SYSTEMS EXAM 2025 |
ALL QUESTIONS AND CORRECT ANSWERS (ALREADY
GRADED A+) | VERIFIED ANSWERS | LATEST EXAM
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - (answers)OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES
FOR A MIN. OF __________ YEARS. - (answers)3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - (answers)IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - (answers)1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - (answers)1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO
SERVICE WITHIN ______ HOURS. - (answers)8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. -
(answers)OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________
DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - (answers)30
WHAT DOES "OOS" STAND FOR? - (answers)OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER -
(answers)TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND
ANY SECTIONAL VALVES. - (answers)MASTER FIRE SUPPRESSION PIPING
,2|Page
CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER. - (answers)DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - (answers)NO IMPAIRMENT WAS
FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - (answers)MAIN CONTROL
VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG
PLACED ON THE MAIN CONTROL VALVE. - (answers)RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - (answers)WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - (answers)BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. - (answers)INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - (answers)IMPAIRMENT
COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER
THAN ________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. -
(answers)50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
____________. - (answers)MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE
DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - (answers)RECORDS
, 3|Page
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. - (answers)REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD
THE FOLLOWING CERTS: - (answers)REFRIGERATION OPERATING ENGINEER, HIGH
PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING
ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS. - (answers)MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES
WITH _________ SPRINKLER HEADS OR LESS. - (answers)30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN
SPRINKLERS ARE INSTALLED. - (answers)96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO PREVENT
THE SYSTEM FROM FREEZING. - (answers)40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. -
(answers)COLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - (answers)DRY PIPE
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. -
(answers)AIR PRESSURE
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE ALARM IS
TRANSMITTED DIRECTLY TO THE _________. - (answers)FIRE DEPARTMENT
DRY PIPE VALVES ARE OF A ______ DESIGN. - (answers)CLAPPER
DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL TRIP
LEVEL. - (answers)15-20