Sprinkler Quiz Solved 100% Correct
________________ fire pumps must be operated in a low-flow condition for 30 minutes
on a weekly basis. - ANSWER-Diesel Engine Equipped
A fire sprinkler system includes a water supply source, a water control valve, a water
flow alarm, and a _______. - ANSWER-Drain
A horizontal elbow in the suction line of a fire pump must be installed at least _______
prior to the suction flange - ANSWER-10 suction pipe diameters
Air pressure gauges on a dry pipe system must be tested or replaced every _______
years. - ANSWER-5 years
An internal inspection of preaction or deluge valves that can be reset without removing
the face plate is permitted to performed _________. - ANSWER-Annually
Any sprinkler system with more than ________ sprinkler must be equipped with water-
flow alarm. - ANSWER-20 sprinkler heads
Clearance between sprinkler deflectors and the top of storage must be _______ or
greater for special sprinklers. - ANSWER-36 inches
Control valve tamper switches must be tested ____________ at minimum. - ANSWER-
Semi-annual
Dry sprinklers must be tested or replaced at ________ years of service and every 10
years thereafter. - ANSWER-10
Each control valve must be operated _______ through it's full range and returned to its
normal position. - ANSWER-Annually
How many test points are required for an antifreeze with a capacity of 475 gallons? -
ANSWER-
Pump room or house for an electric motor driven fire pump used for a warehouse must
be inspected ________. - ANSWER-
The heating system for a water storage tank must be capable of maintaining the water
temperature at a minimum of _______. - ANSWER-42 degrees Fahrenheit
The hydraulic design information sign for a standpipe system must be inspected
_______. - ANSWER-Annually
________________ fire pumps must be operated in a low-flow condition for 30 minutes
on a weekly basis. - ANSWER-Diesel Engine Equipped
A fire sprinkler system includes a water supply source, a water control valve, a water
flow alarm, and a _______. - ANSWER-Drain
A horizontal elbow in the suction line of a fire pump must be installed at least _______
prior to the suction flange - ANSWER-10 suction pipe diameters
Air pressure gauges on a dry pipe system must be tested or replaced every _______
years. - ANSWER-5 years
An internal inspection of preaction or deluge valves that can be reset without removing
the face plate is permitted to performed _________. - ANSWER-Annually
Any sprinkler system with more than ________ sprinkler must be equipped with water-
flow alarm. - ANSWER-20 sprinkler heads
Clearance between sprinkler deflectors and the top of storage must be _______ or
greater for special sprinklers. - ANSWER-36 inches
Control valve tamper switches must be tested ____________ at minimum. - ANSWER-
Semi-annual
Dry sprinklers must be tested or replaced at ________ years of service and every 10
years thereafter. - ANSWER-10
Each control valve must be operated _______ through it's full range and returned to its
normal position. - ANSWER-Annually
How many test points are required for an antifreeze with a capacity of 475 gallons? -
ANSWER-
Pump room or house for an electric motor driven fire pump used for a warehouse must
be inspected ________. - ANSWER-
The heating system for a water storage tank must be capable of maintaining the water
temperature at a minimum of _______. - ANSWER-42 degrees Fahrenheit
The hydraulic design information sign for a standpipe system must be inspected
_______. - ANSWER-Annually