S12 sprinkler test Exam Questions And Correct Answer fire department connection - Answer -normally on exterior of building... FDNY can pump supplemental water into the sprinkler system, standpipe, or other system furnishing water for fire extinguishment to supplement existing water supplies. system control valve - Answer -valve controlling flow to water-based fire protection systems. fire command center - Answer -... MFSPC - Answer -... MLP - Answer -... tags - Answer -on closed section valves serving affected areas: area affected, brief description, occupancy classification, c of f number, estimated time until operational Green tag - Answer -no impairment found in entire system- main control valve white tag - Answer -fully out of service- place on all fire department connecitons red tag - Answer -place on main control valve if FULLY OR PARTIALLY out of service... put sprinkler company name, date of removal from service and anticipated time to operational blue disk - Answer -partially out of service- on all fire department connections water storage tank - Answer -... OS & Y valve - Answer -indicating type of control valve used for fire sprinkler system deluge valve - Answer -water supply control valve intended to be operated by actuation of an automatic detection system that is installed in the same area as the discharge devices. INTENDED USE IS MANUAL AND AUTO deluge sprinkler system - Answer -employing open sprinklers that are attached to a piping system that is connected to a water supply through a valve that is opened by the operation of a detection system installed in the same areas as the sprinklers. WHEN IT OPENS, water flows into the piping system and discharges from all sprinklers attached. Early suppresion fast response sprinklers - Answer -fast response sprinkler that is listed for its capability to provide fire suppression of specific high challenge fire hazards extra large orifice sprinklers - Answer -= or 1 inch less pressure to achieve a given discharge density extended coverage sprinkler - Answer -400 max square feet discharge

Vista previa del contenido

Sprinkler test Question And Correct
Solutions
Class 1 commodity is more combustible then class 3 - Answer -✔✔False

All holes for lag screws shall be pre-drilled __________ inch less in diameter than the
max. root diameter of the lag screw thread. - Answer -✔✔1/8in

Coach screws shall not be used for support of pipes larger than ________ inch in
diameter. - Answer -✔✔4

Distance between supports on a riser shall not exceed _________ feet. - Answer -
✔✔25ft

Fire department connections shall be installed so that they are located not less than
______ nor more than ______ above the level of the adjoining ground, sidewalk, or
grade surface. - Answer -✔✔18in , 48in

Flexible couplings shall be installed on risers within_____ inches above and _____
inches below the floor in multi-story buildings. - Answer -✔✔12in and 24in

For ESFR sprinklers, the clearance between the deflector and the top of storage shall
be ____ inches or greater - Answer -✔✔36in

For extra hazard occupancies, the maximum distance between sprinklers shall not
exceed ______ feet - Answer -✔✔12ft

Hangers shall be designed to support _______ times the weight of water-filled pipe plus
________ at each point of piping support. - Answer -✔✔5 and 250

Hose connections and hose stations shall be unobstructed and shall be located not less
than ______ nor more than ______ above the floor.
Answers - Answer -✔✔36in, 60in

How high can storage be before it is considered high-piled storage? - Answer -✔✔12ft

How shall the sprinkler head protecting the dry pipe valve enclosure be fed? - Answer -
✔✔From the dry side of the system

In residential applications, fire department connections are required to be a minimum of
_______ in size. - Answer -✔✔1 1/2"

, Is the use of reconditioned valves and devices as replacement equipment in existing
systems allowed? - Answer -✔✔Yes

Joints for the connection of copper pipe an fittings on dry and preaction systems shall
be brazed. - Answer -✔✔True

Lateral sway bracing shall be spaced at a minimum of __________ feet on center on all
feed and cross mains regardless of size and on all piping 2 1/2" and larger - Answer -
✔✔40ft

Lateral sway bracing shall not apply to pipes individually supported by rods less than
______ inches long measured between the top of the pipe and the point of attachment
to the building structure. - Answer -✔✔6in

Longitudinal sway bracing spaced at a maximum of ________ feet on center shall be
provided for feed and cross mains. - Answer -✔✔80ft

No clearance is required if flexible couplings are located within _____ each side of a
wall, floor, platform, or foundation. - Answer -✔✔12in

Ordinary hazard occupancy protection areas shall not exceed ________ square feet. -
Answer -✔✔130

Pressure tanks should be kept ________ full of water. - Answer -✔✔2/3

Pressure tanks should maintain an air pressure of at least ______ psi. - Answer -
✔✔75PSI

Risers shall be supported by pipe clamps or by hangers located on the horizontal
connections within ________ inches of the centerline of the riser. - Answer -✔✔24in

Screwed unions shall not be used on pipe larger than _________ inch - Answer -✔✔2in

Sprinklers installed where maximum ambient ceiling temperatures do not exceed 100
degrees farenheit shall be __________ temperature rated sprinklers. - Answer -
✔✔Ordinary

Sprinklers under glass or plastic skylights exposed to direct rays of the sun shall be of
____________ temperature classification. - Answer -✔✔intermediate

Starter lengths less than ____ feet shall not require a hanger - Answer -✔✔6ft

The distance between the last lateral sway brace and the end of the pipe shall not
exceed _______ feet - Answer -✔✔6

Información del documento

Subido en
14 de enero de 2025
Número de páginas
11
Escrito en
2024/2025
Tipo
Examen
Contiene
Preguntas y respuestas
$10.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Vendido
0
Seguidores
0
Artículos
88
Última venta
-



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes