S-12 CITYWIDE SPRINKLER SYSTEMS,
S12 sprinkler test questions with
answers


THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS. - ** VERIFIED ANSWERS **✔✔OWNER



RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A
MIN. OF __________ YEARS. - ** VERIFIED ANSWERS **✔✔3



THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - ** VERIFIED ANSWERS **✔✔IMPAIRMENT COORDINATOR



REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S)
ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - ** VERIFIED ANSWERS **✔✔1



SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - ** VERIFIED ANSWERS **✔✔1



NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO
SERVICE WITHIN ______ HOURS. - ** VERIFIED ANSWERS **✔✔8



FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY
REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. - ** VERIFIED ANSWERS
**✔✔OWNER OF THE BUILDING



IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR
IT WILL BE CONSIDERED AN IMPAIRMENT. - ** VERIFIED ANSWERS **✔✔30

,WHAT DOES "OOS" STAND FOR? - ** VERIFIED ANSWERS **✔✔OUT OF SERVICE



OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS,
SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - ** VERIFIED ANSWERS **✔✔TAGS



A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY
SECTIONAL VALVES. - ** VERIFIED ANSWERS **✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR



__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER. - ** VERIFIED ANSWERS **✔✔DRAIN TEST RESULTS



GREEN TAGS INDICATE THAT __________. - ** VERIFIED ANSWERS **✔✔NO IMPAIRMENT
WAS FOUND



GREEN TAGS WILL BE PLACED ON THE ____________. - ** VERIFIED ANSWERS **✔✔MAIN
CONTROL VALVE



SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG
PLACED ON THE MAIN CONTROL VALVE. - ** VERIFIED ANSWERS **✔✔RED



A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS FULLY OUT OF SERVICE. - ** VERIFIED ANSWERS **✔✔WHITE



A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS PARTIALLY OUT OF SERVICE. - ** VERIFIED ANSWERS **✔✔BLUE



THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL
STATION AND OCCUPANTS. - ** VERIFIED ANSWERS **✔✔INSURANCE

, PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - ** VERIFIED ANSWERS
**✔✔IMPAIRMENT COORDINATOR



GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN
________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - ** VERIFIED
ANSWERS **✔✔50, 40



THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
____________. - ** VERIFIED ANSWERS **✔✔MAIN CONTROL VALVE



__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT.
THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - ** VERIFIED ANSWERS
**✔✔RECORDS



FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT
PROCEEDINGS. - ** VERIFIED ANSWERS **✔✔REVOCATION



THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE
FOLLOWING CERTS: - ** VERIFIED ANSWERS **✔✔REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.



A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND
SPRINKLER SYSTEMS. - ** VERIFIED ANSWERS **✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)



A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH
_________ SPRINKLER HEADS OR LESS. - ** VERIFIED ANSWERS **✔✔30



ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN
SPRINKLERS ARE INSTALLED. - ** VERIFIED ANSWERS **✔✔96

Información del documento

Subido en
2 de diciembre de 2024
Número de páginas
22
Escrito en
2024/2025
Tipo
Examen
Contiene
Preguntas y respuestas
$16.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
EXAMSTUDYPLUG
4.5
(242)
Vendido
385
Seguidores
107
Artículos
20871
Última venta
2 semanas hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes