S-12 CITYWIDE SPRINKLER SYSTEMS,
S12 sprinkler test questions with
answers
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS. - ** VERIFIED ANSWERS **✔✔OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A
MIN. OF __________ YEARS. - ** VERIFIED ANSWERS **✔✔3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - ** VERIFIED ANSWERS **✔✔IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S)
ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - ** VERIFIED ANSWERS **✔✔1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - ** VERIFIED ANSWERS **✔✔1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO
SERVICE WITHIN ______ HOURS. - ** VERIFIED ANSWERS **✔✔8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY
REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. - ** VERIFIED ANSWERS
**✔✔OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR
IT WILL BE CONSIDERED AN IMPAIRMENT. - ** VERIFIED ANSWERS **✔✔30
,WHAT DOES "OOS" STAND FOR? - ** VERIFIED ANSWERS **✔✔OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS,
SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - ** VERIFIED ANSWERS **✔✔TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY
SECTIONAL VALVES. - ** VERIFIED ANSWERS **✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER. - ** VERIFIED ANSWERS **✔✔DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - ** VERIFIED ANSWERS **✔✔NO IMPAIRMENT
WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - ** VERIFIED ANSWERS **✔✔MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG
PLACED ON THE MAIN CONTROL VALVE. - ** VERIFIED ANSWERS **✔✔RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS FULLY OUT OF SERVICE. - ** VERIFIED ANSWERS **✔✔WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS PARTIALLY OUT OF SERVICE. - ** VERIFIED ANSWERS **✔✔BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL
STATION AND OCCUPANTS. - ** VERIFIED ANSWERS **✔✔INSURANCE
, PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - ** VERIFIED ANSWERS
**✔✔IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN
________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - ** VERIFIED
ANSWERS **✔✔50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
____________. - ** VERIFIED ANSWERS **✔✔MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT.
THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - ** VERIFIED ANSWERS
**✔✔RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT
PROCEEDINGS. - ** VERIFIED ANSWERS **✔✔REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE
FOLLOWING CERTS: - ** VERIFIED ANSWERS **✔✔REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND
SPRINKLER SYSTEMS. - ** VERIFIED ANSWERS **✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH
_________ SPRINKLER HEADS OR LESS. - ** VERIFIED ANSWERS **✔✔30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN
SPRINKLERS ARE INSTALLED. - ** VERIFIED ANSWERS **✔✔96
S12 sprinkler test questions with
answers
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS. - ** VERIFIED ANSWERS **✔✔OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A
MIN. OF __________ YEARS. - ** VERIFIED ANSWERS **✔✔3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - ** VERIFIED ANSWERS **✔✔IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S)
ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - ** VERIFIED ANSWERS **✔✔1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - ** VERIFIED ANSWERS **✔✔1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO
SERVICE WITHIN ______ HOURS. - ** VERIFIED ANSWERS **✔✔8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY
REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. - ** VERIFIED ANSWERS
**✔✔OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR
IT WILL BE CONSIDERED AN IMPAIRMENT. - ** VERIFIED ANSWERS **✔✔30
,WHAT DOES "OOS" STAND FOR? - ** VERIFIED ANSWERS **✔✔OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS,
SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - ** VERIFIED ANSWERS **✔✔TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY
SECTIONAL VALVES. - ** VERIFIED ANSWERS **✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER. - ** VERIFIED ANSWERS **✔✔DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - ** VERIFIED ANSWERS **✔✔NO IMPAIRMENT
WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - ** VERIFIED ANSWERS **✔✔MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG
PLACED ON THE MAIN CONTROL VALVE. - ** VERIFIED ANSWERS **✔✔RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS FULLY OUT OF SERVICE. - ** VERIFIED ANSWERS **✔✔WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS PARTIALLY OUT OF SERVICE. - ** VERIFIED ANSWERS **✔✔BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL
STATION AND OCCUPANTS. - ** VERIFIED ANSWERS **✔✔INSURANCE
, PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - ** VERIFIED ANSWERS
**✔✔IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN
________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - ** VERIFIED
ANSWERS **✔✔50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
____________. - ** VERIFIED ANSWERS **✔✔MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT.
THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - ** VERIFIED ANSWERS
**✔✔RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT
PROCEEDINGS. - ** VERIFIED ANSWERS **✔✔REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE
FOLLOWING CERTS: - ** VERIFIED ANSWERS **✔✔REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND
SPRINKLER SYSTEMS. - ** VERIFIED ANSWERS **✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH
_________ SPRINKLER HEADS OR LESS. - ** VERIFIED ANSWERS **✔✔30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN
SPRINKLERS ARE INSTALLED. - ** VERIFIED ANSWERS **✔✔96