bBonding jumpers on the supply side of the service are sized according to NEC® Table ___. -
250.102(C)(1)



Section 250.96(B) permits equipment to be ___ in order to minimize electromagnetic interference (often
called "noise"). - isolated



The size of bonding jumpers on the line or supply side of service equipment is based on the size of the
___. - supply conductor



Section 250.90 requires that an equipment bonding jumper be sized to carry the circuit current that it
must carry during normal circuit operation. - False



Refer to Figure 307.32. If you are to size the bonding jumpers from the conduits in Section 1 to the
equipment grounding busbar, you would use NEC® Section ___ to determine the minimum size of the
BJs. - 250.102(C)



The conductors at Point B in Figure 307.53 are on the ___ side of the service equipment. - load



Metal raceways enclosing GECs are considered to be on the ___ of the service equipment. - line



A branch circuit is installed using metal conduit that will serve as the EGC. A separate EGC was not pulled
in with the circuit conductors. However, a short section of flexible nonmetallic conduit was used in the
middle of the run. When a bonding jumper is installed around the short section of flexible nonmetallic
conduit, the jumper is in ___ with the EGC (metal conduit). - series



Which of the following Code Sections requires the non-current-carrying metal parts of the service
equipment to be bonded together? - 250.92(A)

, The Article 100 definition of bonding emphasizes ___. - electrical continuity



Which of the following tables is used to select a supply-side equipment bonding jumper? - Table
250.102(C)(1)



When grounding electrode conductors are installed in metal conduit for physical protection, the conduit
must be ___. - both a and b



Refer to Figure 205.17. The minimum size bonding jumper for each FMC between the transformer and
Panel LK is ___ AWG. - 2



The MAIN in the switchgear shown in Figure 307.32 is rated at 1600 amps and each conduit contains 600
kcmil conductors. The minimum size of each of the BJs shown in Section 1 is ___ AWG or kcmil. - 1/0



A 120/208-volt switchgear is shown in Figure 307.32. The 1000-amp main is fed with parallel sets of 300
kcmil THHN/THWN aluminum conductors. The minimum size of each of the copper conductors
connected between the ground bar and each service pipe is ___ AWG. - 2



What Code reference requires CATV ground rods to be connected to the building service ground rod, as
one method of tying the two systems together? - 820.93



In general, bonding requirements for the supply (line) side of the service equipment are ___ bonding
requirements on the load side. - more stringent than



Section 250.97 requires a bonding jumper to be used to provide continuity around knockouts, except
where the largest knockout is used or the enclosure is listed for use without bonding. This applies for
circuits of which of the following voltage systems?

I. 120/240 V, 1Ø, 3-W II. 208Y/120 V, 3Ø, 4-W III. 480Y/277 V, 3Ø, 4-W - III only



A 600-amp, 120/240-volt, 3Ø, 4-wire service is to be installed in two conduits. The service-entrance
conductors installed are 350 kcmil. The two threaded RMC conduits enter the bottom of the CT can
where a hole saw was used to cut the holes. The hole saw "walked" a bit and wallowed out the holes so
that now you will have to install bonding bushings on the conduits.

Información del documento

Subido en
15 de noviembre de 2024
Número de páginas
6
Escrito en
2024/2025
Tipo
Examen
Contiene
Preguntas y respuestas
$9.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
edunurse
3.6
(19)
Vendido
156
Seguidores
13
Artículos
6803
Última venta
1 día hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes