Fire Pump Ohio Test Study Guide
Exam
Per NFPA 20 requirements, which of the following is required to illuminate a
pump room or pump house. - -Artificial Light
- Before shipment from the factory, each pump shall be hydrostatically
tested by the manufacturer. The test pressure shall not be less than one-half
times the sum of the pump's shutoff heads plus its maximum allowable
suction head, but shall not be less than, - -200 PSI
- The weekly test for an electric pump requires the pump to run for a
minimum of - -10 Minutes
- The distance between the bottom of strainer and the bottom of the wet pit
on a vertical shaft turbine pump should be: - -One half of the pump diameter
but not less than 12 inches
- Engine generator sets supplying emergency or standby power to fire pump
assemblies shall be periodically tested in accordance with which of the
following NFPA standards: - -NFPA 110
- A pump for fire protection shall be selected to operate at less than or equal
to _% of the rated capacity. - -150
- A fire pump controller shall be permitted to be used as a junction box to
supply other equipment. - -False
- Authority Having Jurisdiction (AHJ) is the organization, office, or individual
responsible for approving equipment, materials, installations or procedures. -
-True
- Which of the following conditions requires the installation of a listed
indicating butterfly or gate valve and a drain valve or ball drip located in the
pipeline to the hose valve header: - -Both A and B
- The maximum allowable shutoff head for a pump with a rated capacity of
900 gpm and a rated head of 250 feet is: - -350 Feet
- Maximum number of drivers permitted to equip a fire pump is - -One
- Which of the following valves allows the diversion of liquid to limit excess
pressure in a system: - -A relief valve
Exam
Per NFPA 20 requirements, which of the following is required to illuminate a
pump room or pump house. - -Artificial Light
- Before shipment from the factory, each pump shall be hydrostatically
tested by the manufacturer. The test pressure shall not be less than one-half
times the sum of the pump's shutoff heads plus its maximum allowable
suction head, but shall not be less than, - -200 PSI
- The weekly test for an electric pump requires the pump to run for a
minimum of - -10 Minutes
- The distance between the bottom of strainer and the bottom of the wet pit
on a vertical shaft turbine pump should be: - -One half of the pump diameter
but not less than 12 inches
- Engine generator sets supplying emergency or standby power to fire pump
assemblies shall be periodically tested in accordance with which of the
following NFPA standards: - -NFPA 110
- A pump for fire protection shall be selected to operate at less than or equal
to _% of the rated capacity. - -150
- A fire pump controller shall be permitted to be used as a junction box to
supply other equipment. - -False
- Authority Having Jurisdiction (AHJ) is the organization, office, or individual
responsible for approving equipment, materials, installations or procedures. -
-True
- Which of the following conditions requires the installation of a listed
indicating butterfly or gate valve and a drain valve or ball drip located in the
pipeline to the hose valve header: - -Both A and B
- The maximum allowable shutoff head for a pump with a rated capacity of
900 gpm and a rated head of 250 feet is: - -350 Feet
- Maximum number of drivers permitted to equip a fire pump is - -One
- Which of the following valves allows the diversion of liquid to limit excess
pressure in a system: - -A relief valve