Exam Questions And Answers
Vertical openings connecting four or more floors require ? rated walls - ANS 2 hour
New and existing vertical openings require a __________ rated enclosure as long as there are
_______ stories or less - ANS 1 hour/ 3 stories
Hazardous areas such as boiler rooms fuel fired heater rooms, bulk laundires (larger than 100
sq ft) require a ________ rated walls and a _______ rated door - ANS 1 hour/3/4 hours
flamable liquid storage terms. new and existing, require _____ rated walls and _____ rated
doors - ANS 2 hour/1 1/2 hour
Existing labs, that are not a severe hazard require ______ walls and _____ rated doors (new
only need what) - ANS 1 hour/ 3/4 hour/ resist passage or smoke
Icons used in the HAS manual- Scoring categories.
Category A- usually related to ________
Category C- are - ANS a- usually related to structural requirements (policies, programs or
plans) addresses issues that must be fully compliant
c- are frequency based requirements and are scored lowered on the number of times a hospital
is found not to be compliant with a particular EP
Soiled linens and trash receptacles larger than 32 gallons must be located in a room protected
as a ________ - ANS hazardous area (1 hour rated walls, 3/4 hour rated doors)
New elevators must be equipped with the following four items - ANS 1) firefighter service
key and smoke detector automatic recall
2) firefighter service emergency in can key operation
3) machine room smoke detectors
4) elevator lobby smoke detectors
Travel distance from any point to the nearest fire extinguisher is ________ or less - ANS 75'
Maintaining equipment for extinguishing fires.
limited area sprinkler systems- connected to domestic water supply must have a _____ and
have nor more than ______ sprinkler heads - ANS shut off valves/6(six)