State the main reason why a large industrial electrical installation has a higher
prospective short circuit current (PSSC) than a domestic electrical installation.
Right Ans - The fault loop impedance is lower
Because the distribution transformer is close to the installation or on-site

A CT metering circuit is measuring the consumption of an industrial electrical
installation at near to full load. The CT secondary must be shortcircuited
before disconnecting the meters from the CT. State TWO reasons why the CT
secondary must be short-circuited Right Ans - To prevent a high voltage
developing in the circuit.
To prevent damage to the CT winding insulation.

A result of fault loop impedance test at the main switchboard of a low voltage
electrical installation will show the prospective short circuit current level of
the installation or the impedance of the fault loop at the switchboard under
fault conditions. State the main purpose of the information gained from the
earth fault loop impedance test Right Ans - To confirm that the protective
devices can safely interrupt the installation PSSC.

Some protective devices in an electrical installation have a fault duty lower
than the prospective short circuit rating of the installation. State the main
hazard that could occur when a high prospective short-circuit fault current
occurs in the electrical installation. Right Ans - Flash over on switchboards
due to inadequate kA rating of protective devices

AS/NZS 3000 requires that a test voltage of 500V d.c. is used for an insulation
resistance test of a low voltage electrical installation.
Explain why a voltage of 500V is applied. Right Ans - To stress the
insulation at a voltage above 325V a.c. (or peak a.c. voltage.

AS/NZS 3000 requires that a test voltage of 500V d.c. is used for an insulation
resistance test of a low voltage electrical installation.
Explain why the voltage is a d.c. voltage. Right Ans - To ensure capacitive or
inductive reactance does not influence the test result.
A constant maximum voltage is a more stringent test than the momentary
peaks of an a.c. waveform.

, AS/NZS 3000 requires that a test voltage of 500V d.c. is used for an insulation
resistance test of a low voltage electrical installation.
Define the term current rating as it applies to an HRC fuse? Right Ans - This
is the maximum current that the fuse is designed to carry continuously

AS/NZS 3000 requires that a test voltage of 500V d.c. is used for an insulation
resistance test of a low voltage electrical installation.
Define the term breaking (or rupturing) capacity as it applies to an HRC fuse
Right Ans - The maximum fault current the fuse can safely interrupt.

State TWO technical advantages that a soft starter has when compared to and
electromechanical type starter, such as auto-transformer. Right Ans -
Broad range of options for starting and stopping
Broad range of options for protection.
Visual feedback of key technical parameters.
Smoother starting
Reduced mechanical stress on equipment on starting. Reduced electrical
stress on equipment on starting

Explain the purpose of an interlocks in a star/delta starter Right Ans - To
prevent the star and delta contactors closing simultaneously

State the effect of the interlocks failing in a star/delta starter Right Ans - An
electrical interlock failure could prevent the motor starting. An electrical
interlock failure could cause a phase-to-phase short.
A mechanical interlock failure could prevent the motor starting.
A mechanical interlock failure could cause a phase-to-phase short.

Define the term pullout torque as it applies to an a.c. induction motor Right
Ans - The maximum torque the motor can develop.

State the synchronous speed of a three-phase, four-pole, 50 Hz motor.
Right Ans - 1500 rpm

State the Standard and section of that Standard that specifies the tests and
checks that need to be carried out on the socket outlet and final subcircuit
wiring. Right Ans - AS/NZS 3000
Section 8

Información del documento

Subido en
9 de octubre de 2024
Número de páginas
5
Escrito en
2024/2025
Tipo
Examen
Contiene
Preguntas y respuestas
$10.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
NorthWest
4.1
(174)
Vendido
847
Seguidores
673
Artículos
6771
Última venta
1 mes hace




Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes