S-12 CITYWIDE SPRINKLER SYSTEMS, S12 sprinkler test Questions and Correct Answers &
Latest Updated
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS.
o :## OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN.
OF __________ YEARS.
o :## 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS.
o :## IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE
CONSIDERED PLANNED REMOVAL FROM SERVICE.
o :## 1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED
OUT OF SERVICE CONDITIONS.
o :## 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE
WITHIN ______ HOURS.
Master01: DO NOT COPY AND PASTE!! August 25, 2024 Latest Update
,2|Page: 2024/2025 Grade A+
o :## 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT
CONDITION TO THE ___________ AND THE FIRE DEPT.
o :## OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT
WILL BE CONSIDERED AN IMPAIRMENT.
o :## 30
WHAT DOES "OOS" STAND FOR?
o :## OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS,
SYS. CONTROL VALVES, AND FIRE COMMAND CENTER
o :## TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY
SECTIONAL VALVES.
o :## MASTER FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW
PRESSURES BEFORE AND AFTER.
o :## DRAIN TEST RESULTS
Master01: DO NOT COPY AND PASTE!! August 25, 2024 Latest Update
,3|Page: 2024/2025 Grade A+
GREEN TAGS INDICATE THAT __________.
o :## NO IMPAIRMENT WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________.
o :## MAIN CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG PLACED
ON THE MAIN CONTROL VALVE.
o :## RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS FULLY OUT OF SERVICE.
o :## WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS PARTIALLY OUT OF SERVICE.
o :## BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL
STATION AND OCCUPANTS.
o :## INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT
NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED.
Master01: DO NOT COPY AND PASTE!! August 25, 2024 Latest Update
, 4|Page: 2024/2025 Grade A+
o :## IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN
________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING.
o :## 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
____________.
o :## MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT.
THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS.
o :## RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT
PROCEEDINGS.
o :## REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE
FOLLOWING CERTS:
o :## REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND
NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND
SPRINKLER SYSTEMS.