Backflow
A check valve on a double check valve assembly is considered
"tight" if... - CORRECT ANSWER-It is drip tight at 1.0 psi differential



A cross connection means... - CORRECT ANSWER-A physical
arrangement whereby the potable water supply is connected,
directly or indirectly, continuously or intermittently with nonpotable
water or a secondary water source.



A leaky check valve on a double check assembly could be
attributed to... - CORRECT ANSWER-Number 2 shut-off valve
leaks



A pressure vacuum breaker may be used on a pressure connection.
T o F? - CORRECT ANSWER-True



A pressure vacuum breaker should have a minimum of how many
inches between its "critical level" and the overflow rim of an open
tank of chronic acid, used in the process of polishing steel plates? -
CORRECT ANSWER-12 inches



A purpose of the number three test cock on a PVB is to detect a
leaky downstream shut-off valve. T o F? - CORRECT
ANSWER-False

, A reduced pressure principle device must be installed at least: -
CORRECT ANSWER-12 inches above the floor



A secondary source of supply, such as a well, does not require
protection from backflow. T o F? - CORRECT ANSWER-False



A shut-off valve may be maintained downstream from a pressure
vacuum breaker; however, there shall be no possibility of imposing
pressure by pump or other means downstream from the device. T o
F? - CORRECT ANSWER-True



A tester arrives to test a reduced pressure principle device which
has been out of service. The tester opens the #1 shutoff valve to
establish water pressure within the device. Upon opening the valve,
the relief port continuously vents water. This venting is: - CORRECT
ANSWER-An indication of a fouled relief valve or fouled leaky #1
check valve



A USC Foundation for Cross-Connection & Hydraulic Research
(FCCCHR) approved device consisting of two independently
operating, internally-loaded check valves located between two
tightly closing shut-off valves, with four appropriately located test
cocks is a: - CORRECT ANSWER-Double check valve assembly



A vacuum relief valve is designed and approved for use as a
back-flow preventer. T o F? - CORRECT ANSWER-False

Información del documento

Subido en
18 de julio de 2024
Número de páginas
12
Escrito en
2023/2024
Tipo
Examen
Contiene
Preguntas y respuestas
$8.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
scholartutor
4.8
(923)
Vendido
2789
Seguidores
3
Artículos
10768
Última venta
3 semanas hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes