EPA 608 TYPE III EXPECTED QUESTIONS WITH
VERIFIED ANSWERS

Question 1.
What steps may be taken to prevent air accumulation into an idle low pressure refrigeration system?
a) Leave the purge unit on-line at all times.
b) System pressure should be maintained slightly above atmospheric.
c) Open the air vents on the condenser.
d) Intermittently operate the system with no load.

ANSWER
b) System pressure should be maintained slightly above atmospheric.



Question 2.
If you suspect a leak in the water box of a chiller, you should place the leak detector probe _________,
and sniff for refrigerants.

a) at the rupture disc
b) through the vent valve
c) through a test plug
d) through a drain valve

ANSWER
d) through a drain valve



Question 3.
What refrigerant(s) require an equipment room refrigeration sensor (as per ASHRAE Standard 15)?

1) R-12
2) R-134a
3) R-123
4) none of the above
5) all of the above
6) only 2 and 3

ANSWER
3) R-123






,Question 4.
According to ASHRAE Guideline 3-1996, if the pressure in a system rises from 1 mm Hg to above
__________ during a standard vacuum test, the system should be checked for leaks.

1) 1.5 mm Hg
2) 2.2 mm HG
3) 2.5 mm Hg
4) 0.5 mm Hg

ANSWER
3) 2.5 mm Hg



Question 5.
Under what code group of ASHRAE Standard 34 does R-123 fall?

1) A1
2) A2
3) B1
4) G2
5) B2
6) B123

ANSWER
3) B1



Question 6.
A hydrostatic tube test kit is used to: _________.

a) blow all water from the tubes
b) remove any water from the machine
c) vent refrigerant
d) determine if a tube leaks

ANSWER
d) determine if a tube leaks






,Question 7.
If you are using a water-cooled recovery unit, __________ is the primary water source for the recovery
unit's condensing coil.

1) chilled water
2) condenser water
3) local municipal water supply
4) de-ionized water
5) bottled water

ANSWER
3) local municipal water supply



Question 8.
What refrigerant(s) require an equipment room oxygen deprivation sensor (as per ASHRAE Standard
15)?
1) R-12
2) R-134a
3) R-11
4) none of the above
5) all of the above
6) only 2 and 3

ANSWER
5) all of the above



Question 9.
A system does not have to be evacuated all the way to the required level when: __________.

a) the repair is major
b) the repair is followed by an evacuation of the appliance to the environment
c) the appliance is being disposed of
d) leaks in the appliance make evacuation to the prescribed level unattainable

ANSWER
d) leaks in the appliance make evacuation to the prescribed level unattainable






, Question 10.
Which repair is a "major" repair under EPA's regulations?

1) Replacement of an evaporator coil.
2) Replacement of a filter-drier greater than 8 cubic inches,
3) Replacement of a run or start capacitor.
4) Replacement of a fan or water pump motor.

ANSWER
1) Replacement of an evaporator coil.



Question 11.
The PRIMARY purpose of a purge unit on a CFC-11 chiller is to: ___________.

a) remove CFCs from the system
b) condense air out of the system
c) condense water out of the system
d) remove non-condensables from the system

ANSWER
d) remove non-condensables from the system



Question 12.
After reaching the required recovery vacuum on an appliance, you should _________.

1) immediately disconnect the recycling or recovery equipment and open the system for service
2) wait for at least a few minutes to see if the system pressure rises, indicating that there is still
refrigerant in liquid form or in the oil
3) immediately break the vacuum with nitrogen and open the system for service
4) immediately pressurize the system with nitrogen and perform a leak check

ANSWER
2) wait for at least a few minutes to see if the system pressure rises, indicating that there is
still refrigerant in liquid form or in the oil

Información del documento

Subido en
26 de octubre de 2026
Número de páginas
31
Escrito en
2026/2027
Tipo
Examen
Contiene
Preguntas y respuestas
$17.99

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
Vendido
35
Seguidores
1
Artículos
22648
Última venta
1 día hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes