Question 1

A wet-pipe sprinkler system is supplied by a municipal main with a static pressure of 72 psi and a
residual pressure of 58 psi at 1,000 gpm. Which test information is most critical for hydraulic
calculations under NFPA 13?

A. Water temperature
B. Flow and residual pressure relationship
C. Pipe material only
D. Sprinkler finish

Answer: B

Explanation: NFPA 13 hydraulic calculations depend on water supply characteristics, specifically static
pressure, residual pressure, and corresponding flow. These values establish the water supply curve
used to verify system demand.



Question 2

Under NFPA 13, what is the principal function of a check valve in a fire protection riser assembly?

A. Increase pressure
B. Prevent reverse water flow
C. Reduce pipe friction loss
D. Operate supervisory alarms

Answer: B

Explanation: Check valves prevent reverse flow into water supplies and are commonly used in
backflow prevention assemblies and fire pump discharge piping.



Question 3

An ordinary hazard Group 2 occupancy requires a density of 0.20 gpm/ft² over 1,500 ft². What is the
required system demand before hose allowance?

A. 250 gpm
B. 300 gpm
C. 350 gpm
D. 400 gpm

Answer: B

Calculation:
0.20 × 1,500 = 300 gpm

Explanation: Hydraulic calculations begin by multiplying design density by remote area size.

, F35 Class DF Fire Suppression Installation Contractor
Latest Practice Exam (Updated Edition)


Question 4

Which NFPA standard governs dry chemical extinguishing systems?

A. NFPA 17
B. NFPA 13
C. NFPA 25
D. NFPA 72

Answer: A

Explanation: NFPA 17 provides requirements for installation, testing, maintenance, and operation of
dry chemical fire suppression systems.



Question 5

A contractor is installing a clean agent system protecting a data center. Which standard applies?

A. NFPA 17A
B. NFPA 2001
C. NFPA 96
D. NFPA 24

Answer: B

Explanation: NFPA 2001 governs clean agent extinguishing systems including FM-200, Novec 1230,
and inert gas systems.



Question 6

Which sprinkler orientation is most suitable for exposed piping below ceilings?

A. Concealed
B. Sidewall
C. Upright
D. Flush

Answer: C

Explanation: Upright sprinklers are installed above piping and discharge upward against deflectors.



Question 7

According to OSHA, a trench deeper than what depth generally requires a protective system unless
excavated in stable rock?

, F35 Class DF Fire Suppression Installation Contractor
Latest Practice Exam (Updated Edition)
A. 3 ft
B. 4 ft
C. 5 ft
D. 6 ft

Answer: C

Explanation: OSHA requires trench protection at depths of 5 feet or greater unless stable rock
conditions exist.



Question 8

A sprinkler requiring 25 gpm operates at what minimum pressure if its K-factor is 5.6?

A. 16 psi
B. 20 psi
C. 25 psi
D. 30 psi

Answer: B

Calculation:
Q = K√P

25 = 5.6√P

P ≈ 20 psi



Question 9

Under NFPA 25, how frequently should control valves be visually inspected in most systems?

A. Monthly
B. Weekly or monthly depending on valve supervision
C. Every 5 years
D. Annually

Answer: B

Explanation: NFPA 25 inspection frequency depends on supervision methods and valve types.



Question 10

Which component sends a signal when a control valve changes position?

A. Water motor gong
B. Tamper switch

, F35 Class DF Fire Suppression Installation Contractor
Latest Practice Exam (Updated Edition)
C. Alarm check valve
D. Test header

Answer: B

Explanation: Tamper switches monitor valve position and transmit supervisory signals.



Question 11

A contractor installs Schedule 40 steel pipe instead of Schedule 10 as specified. What is the primary
hydraulic effect?

A. Greater friction loss
B. Lower friction loss due to larger internal diameter reduction resistance
C. No impact
D. Reduced sprinkler flow

Answer: B

Explanation: Pipe wall thickness affects internal diameter, influencing friction loss.



Question 12

Which type of sprinkler is most commonly installed along walls in hotel corridors?

A. Upright
B. Sidewall
C. ESFR
D. Open sprinkler

Answer: B

Explanation: Sidewall sprinklers efficiently protect narrow spaces and corridors.



Question 13

What is the primary purpose of a fire pump churn test?

A. Verify alarm function only
B. Measure no-flow pressure performance
C. Determine sprinkler density
D. Calculate friction loss

Answer: B

Explanation: Churn testing evaluates pump performance without system demand.

Información del documento

Subido en
14 de octubre de 2026
Número de páginas
101
Escrito en
2026/2027
Tipo
Examen
Contiene
Preguntas y respuestas
$76.99

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Vendido
2
Seguidores
0
Artículos
223
Última venta
1 día hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes