Mass oil burner / NFPA 31 & NORA
Study online at https://quizlet.com/_a29phk
1. Cast iron fittings can be used in heating fuel False
systems?
2. Tank vent shall terminate Within 12 feet of the fill and visible from
the fill
3. Tanks exceeding 330 gallons must have Top supply connection
4. Fuel return piping from an appliance shall Enter the top of the tank
5. Oil appliances burning used oil shall only be In commercial or industrial occupancies
installed
6. Technician must be present for filling of new False
oil tank
7. A common tank vent pipe shall be One pipe size larger than the largest in-
dividual vent pipe connected to it
8. If oil supply piping is not visible for inspec- Pressure or vacuum test the line
tion you must
9. Installation instructions for the care and op- True
eration of the appliance must be posted
10. Oil burning appliances shall have Limit control for pressure in steam, tem-
perature in water boiler, and tempera-
ture in furnace
11. Above ground tank installed inside must be Torwards the supply at a pitch of 1/4 inch
pitched per foot
12. Outdoor tanks must be located Five feet from property line for 275g or
smaller, ten feet for more than 275 but
, Mass oil burner / NFPA 31 & NORA
Study online at https://quizlet.com/_a29phk
not exceeding 660g. Must be on con-
crete slab
13. A chimney connector shall maintain a pitch 1/4 inch per foot
or rise of
14. Minimal gauge thickness for steel flue pipe 26 gauge
connectors less than nine inches in diameter
15. Oil fired water heater must be equipped with True
water temp, pressure, and vacuum relief de-
vice
16. Tank vent piping shall be Pitched forward tank, terminate two feet
minimum from building openings, cor-
rosion resistant weatherproof cap
17. Direct vent systems shall terminate 4 feet horizontally from a building open-
ing
18. Fuel can be transferred from tank to appli- False
ance by pressurizing the tank
19. Fusible link safety shutoff valves shall be lo- Within six inches of the filter between the
cated tank and filter
20. Before installation of new oil burner you are Inspect the combustion chamber
required to
21. A crankcase oil burner can be installed in False
any location where a standard oil burner was
located
22. Can tanks be installed in garages
, Mass oil burner / NFPA 31 & NORA
Study online at https://quizlet.com/_a29phk
Yes, if protected from vehicle impacts by
barriers
23. Teflon tape can be used on oil lines False
24. The trial for ignition period for oil burners 15 seconds
less than 20 GPM is?
25. Fusible switches shall operate at a temp of 165F
26. A masonry chimney needs a metal liner False
27. Any valves used on oil burner installation Fusible valve
must be a
28. What form is used to pull an oil burner per- Form 1
mit
29. What size pipe is used to cross connect tank 1/2 inch
outlet piping
30. What is an oil safety valve required On existing installations when a burner,
boiler, furnace or tank is replaced
31. When must you install a draft regulator When not exempted by the manufactur-
er
32. As of January 1 2014, max safety timing for 15 seconds
an oil burner safety switch must be no more
than
33. What type of boiler must be equipped with Water boilers over 400,000 BTU, all
low water cut off steam boiler
34. A draft inducer
Study online at https://quizlet.com/_a29phk
1. Cast iron fittings can be used in heating fuel False
systems?
2. Tank vent shall terminate Within 12 feet of the fill and visible from
the fill
3. Tanks exceeding 330 gallons must have Top supply connection
4. Fuel return piping from an appliance shall Enter the top of the tank
5. Oil appliances burning used oil shall only be In commercial or industrial occupancies
installed
6. Technician must be present for filling of new False
oil tank
7. A common tank vent pipe shall be One pipe size larger than the largest in-
dividual vent pipe connected to it
8. If oil supply piping is not visible for inspec- Pressure or vacuum test the line
tion you must
9. Installation instructions for the care and op- True
eration of the appliance must be posted
10. Oil burning appliances shall have Limit control for pressure in steam, tem-
perature in water boiler, and tempera-
ture in furnace
11. Above ground tank installed inside must be Torwards the supply at a pitch of 1/4 inch
pitched per foot
12. Outdoor tanks must be located Five feet from property line for 275g or
smaller, ten feet for more than 275 but
, Mass oil burner / NFPA 31 & NORA
Study online at https://quizlet.com/_a29phk
not exceeding 660g. Must be on con-
crete slab
13. A chimney connector shall maintain a pitch 1/4 inch per foot
or rise of
14. Minimal gauge thickness for steel flue pipe 26 gauge
connectors less than nine inches in diameter
15. Oil fired water heater must be equipped with True
water temp, pressure, and vacuum relief de-
vice
16. Tank vent piping shall be Pitched forward tank, terminate two feet
minimum from building openings, cor-
rosion resistant weatherproof cap
17. Direct vent systems shall terminate 4 feet horizontally from a building open-
ing
18. Fuel can be transferred from tank to appli- False
ance by pressurizing the tank
19. Fusible link safety shutoff valves shall be lo- Within six inches of the filter between the
cated tank and filter
20. Before installation of new oil burner you are Inspect the combustion chamber
required to
21. A crankcase oil burner can be installed in False
any location where a standard oil burner was
located
22. Can tanks be installed in garages
, Mass oil burner / NFPA 31 & NORA
Study online at https://quizlet.com/_a29phk
Yes, if protected from vehicle impacts by
barriers
23. Teflon tape can be used on oil lines False
24. The trial for ignition period for oil burners 15 seconds
less than 20 GPM is?
25. Fusible switches shall operate at a temp of 165F
26. A masonry chimney needs a metal liner False
27. Any valves used on oil burner installation Fusible valve
must be a
28. What form is used to pull an oil burner per- Form 1
mit
29. What size pipe is used to cross connect tank 1/2 inch
outlet piping
30. What is an oil safety valve required On existing installations when a burner,
boiler, furnace or tank is replaced
31. When must you install a draft regulator When not exempted by the manufactur-
er
32. As of January 1 2014, max safety timing for 15 seconds
an oil burner safety switch must be no more
than
33. What type of boiler must be equipped with Water boilers over 400,000 BTU, all
low water cut off steam boiler
34. A draft inducer