All heating, combustion, and cooking equipment shall be
provided with insulation or the building construction shall
be fire protected, so that during operation the surface of 170 ̊ F
combustible construction materials will not be raised to a
temperature higher than .
Acceptance tests: Boilers shall not be placed in operation
upon completion of construction until they have been
Inspected and tested.
and an equipment use permit has been issued by
the commissioner.
Periodic boiler inspections: All boilers shall be inspected
Once a year.
at least including chimney connections.
Owner's annual statement: The owner of each boiler that
is subject to periodic inspections shall file an annual
Written statement.
with the commissioner, specifying the location of each
boiler and arrangement for inspection.
(1) Tightness of liquid fuel piping.
What three things must be tested for any fuel burning and
(2) Tightness of fuel oil storage tanks.
storage installation before the system can be operated?
(3) Tightness of gas distribution piping.
Cards giving complete instructions for care and operation
What are instruction cards for oil burning systems?
that are permanently located near the equipment.
Every oil burning installation that is not fully automatic or
requires preheating shall be operated by, or under, the
COF
direct supervision of a person holding a issued by
the fire commissioner.
After any fuel burning equipment repair for which a li-
censed operator is required, such operator shall also
Present.
check the repairs and be while the equipment is
started.
1/9
, P-99 / Low PSI Oil Burner Operator Test with Answers Rated A
What is abatement of air contaminants? Compliance with the air pollution control code.
(1) Low Temp: 600° F or less.
What are the 3 equipment classifications and their tem-
peratures for the products of combustion at the point of (2) Medium Temp: 600° - 1000° F.
leaving the equipment?
(3) High Temp: 1000° or greater.
Ventilation shall be capable of providing at least CFM
of air for each gallon of oil per hour required to fire the 36
equipment to gross output.
What is fuel-oil? Hydrocarbon oils with a flashpoint not lower than 100 ̊F.
The use of crankcase refuse oil as fuel-oil is . Prohibited.
Overflow pipes shall not be smaller in size than the
Supply.
pipe.
(1) Low pressure hot water.
Oil is heated in storage tanks by coils using which three
(2) Steam
possible methods?
(3) Electric heaters.
A remote control for oil burner is provided to stop what? The flow of oil to any burner.
(1) Oil temperature.
(2) Ignition.
What are the four safety controls that shall be installed
with each automatic burner?
(3) Stack or combustion.
(4) High temperature or pressure.
No oil burner shall be installed unless it is connected to a
Chimney/smoke stack.
.
Storage tank.
2/9