The purpose of branch circuit load calculations is to determine -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔The size of branch circuit overcurrent
|\ |\ |\ |\ |\ |\ |\ |\
protection and branch circuit conductors using NEC
|\ |\ |\ |\ |\ |\
NEC article 210 - CORRECT ANSWERS ✔✔Covers branch circuits
|\ |\ |\ |\ |\ |\ |\ |\ |\
( except for branch circuits that supplies only motor loads).
|\ |\ |\ |\ |\ |\ |\ |\ |\
NEC section 210.18 - CORRECT ANSWERS ✔✔Branch circuits are
|\ |\ |\ |\ |\ |\ |\ |\ |\
rated by the maximum rating or setting of the over current device
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
NEC section 210.19 - CORRECT ANSWERS ✔✔Branch circuit
|\ |\ |\ |\ |\ |\ |\ |\
conductors are required to be sized with an ampacity rating that is
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
no less than the maximum load to be served
|\ |\ |\ |\ |\ |\ |\ |\
Branch circuit conductors must have an ampacity rating equal to or
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
greater than the non continuous load plus - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
✔✔125% of the continuous load |\ |\ |\ |\
NEC table 210.24 - CORRECT ANSWERS ✔✔Summarize the
|\ |\ |\ |\ |\ |\ |\ |\
branch circuit requirements
|\ |\
, NEC Article 220 - CORRECT ANSWERS ✔✔Includes the
|\ |\ |\ |\ |\ |\ |\ |\
requirements used to determinable the number of branch circuits |\ |\ |\ |\ |\ |\ |\ |\ |\
required and the requirements used to compute branch circuit
|\ |\ |\ |\ |\ |\ |\ |\ |\
feeder and service loads
|\ |\ |\
NEC section 210.20 - CORRECT ANSWERS ✔✔The branch circuit
|\ |\ |\ |\ |\ |\ |\ |\ |\
rating shall not be less than the noncontinuous load plus 125% of
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
continuous load |\
Continuous loads are calculated at - CORRECT ANSWERS |\ |\ |\ |\ |\ |\ |\ |\
✔✔125% of the maximum current rating
|\ |\ |\ |\ |\
Ampacity of branch circuit conductors must be derated when -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔There are more than 3 conductors,
|\ |\ |\ |\ |\ |\ |\ |\
temperature exceeds the temperature rating |\ |\ |\ |\
NEC table 310.16 - CORRECT ANSWERS ✔✔Lists allowable
|\ |\ |\ |\ |\ |\ |\ |\
ampacities for insulated conductors rated 0 to 2,000
|\ |\ |\ |\ |\ |\ |\
If the number of current carrying conductors in the conduit or cable
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
exceeds three it must be - CORRECT ANSWERS ✔✔derated
|\ |\ |\ |\ |\ |\ |\ |\ |\
answers
The purpose of branch circuit load calculations is to determine -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔The size of branch circuit overcurrent
|\ |\ |\ |\ |\ |\ |\ |\
protection and branch circuit conductors using NEC
|\ |\ |\ |\ |\ |\
NEC article 210 - CORRECT ANSWERS ✔✔Covers branch circuits
|\ |\ |\ |\ |\ |\ |\ |\ |\
( except for branch circuits that supplies only motor loads).
|\ |\ |\ |\ |\ |\ |\ |\ |\
NEC section 210.18 - CORRECT ANSWERS ✔✔Branch circuits are
|\ |\ |\ |\ |\ |\ |\ |\ |\
rated by the maximum rating or setting of the over current device
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
NEC section 210.19 - CORRECT ANSWERS ✔✔Branch circuit
|\ |\ |\ |\ |\ |\ |\ |\
conductors are required to be sized with an ampacity rating that is
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
no less than the maximum load to be served
|\ |\ |\ |\ |\ |\ |\ |\
Branch circuit conductors must have an ampacity rating equal to or
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
greater than the non continuous load plus - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
✔✔125% of the continuous load |\ |\ |\ |\
NEC table 210.24 - CORRECT ANSWERS ✔✔Summarize the
|\ |\ |\ |\ |\ |\ |\ |\
branch circuit requirements
|\ |\
, NEC Article 220 - CORRECT ANSWERS ✔✔Includes the
|\ |\ |\ |\ |\ |\ |\ |\
requirements used to determinable the number of branch circuits |\ |\ |\ |\ |\ |\ |\ |\ |\
required and the requirements used to compute branch circuit
|\ |\ |\ |\ |\ |\ |\ |\ |\
feeder and service loads
|\ |\ |\
NEC section 210.20 - CORRECT ANSWERS ✔✔The branch circuit
|\ |\ |\ |\ |\ |\ |\ |\ |\
rating shall not be less than the noncontinuous load plus 125% of
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
continuous load |\
Continuous loads are calculated at - CORRECT ANSWERS |\ |\ |\ |\ |\ |\ |\ |\
✔✔125% of the maximum current rating
|\ |\ |\ |\ |\
Ampacity of branch circuit conductors must be derated when -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔There are more than 3 conductors,
|\ |\ |\ |\ |\ |\ |\ |\
temperature exceeds the temperature rating |\ |\ |\ |\
NEC table 310.16 - CORRECT ANSWERS ✔✔Lists allowable
|\ |\ |\ |\ |\ |\ |\ |\
ampacities for insulated conductors rated 0 to 2,000
|\ |\ |\ |\ |\ |\ |\
If the number of current carrying conductors in the conduit or cable
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
exceeds three it must be - CORRECT ANSWERS ✔✔derated
|\ |\ |\ |\ |\ |\ |\ |\ |\