Cast iron fittings can be used in heating fuel systems? - Answer False Tank vent shall terminate - Answer Within 12 feet of the fill and visible from the fill Tanks exceeding 330 gallons must have - Answer Top supply connection Fuel return piping from an appliance shall - Answer Enter the top of the tank Oil appliances burning used oil shall only be installed - Answer In commercial or industrial occupancies Technician must be present for filling of new oil tank - Answer False A common tank vent pipe shall be - Answer One pipe size larger than the largest individual vent pipe connected to it If oil supply piping is not visible for inspection you must - Answer Pressure or vacuum test the line Installation instructions for the care and operation of the appliance must be posted - Answer True Oil burning appliances shall have - Answer Limit control for pressure in steam, temperature in water boiler, and temperature in furnace Above ground tank installed inside must be pitched - Answer Torwards the supply at a pitch of 1/4 inch per foot Outdoor tanks must be located - Answer Five feet from property line for 275g or smaller, ten feet for more than 275 but not exceeding 660g. Must be on concrete slab A chimney connector shall maintain a pitch or rise of - Answer 1/4 inch per foot

Vista previa del contenido

Mass oil burner / NFPA 31 & NORA
Questions Fully Solved.
Cast iron fittings can be used in heating fuel systems? - Answer False



Tank vent shall terminate - Answer Within 12 feet of the fill and visible from the fill



Tanks exceeding 330 gallons must have - Answer Top supply connection



Fuel return piping from an appliance shall - Answer Enter the top of the tank



Oil appliances burning used oil shall only be installed - Answer In commercial or industrial
occupancies



Technician must be present for filling of new oil tank - Answer False



A common tank vent pipe shall be - Answer One pipe size larger than the largest individual
vent pipe connected to it



If oil supply piping is not visible for inspection you must - Answer Pressure or vacuum test the
line



Installation instructions for the care and operation of the appliance must be posted - Answer
True



Oil burning appliances shall have - Answer Limit control for pressure in steam, temperature in
water boiler, and temperature in furnace



Above ground tank installed inside must be pitched - Answer Torwards the supply at a pitch
of 1/4 inch per foot



Outdoor tanks must be located - Answer Five feet from property line for 275g or smaller, ten
feet for more than 275 but not exceeding 660g. Must be on concrete slab



A chimney connector shall maintain a pitch or rise of - Answer 1/4 inch per foot

,Minimal gauge thickness for steel flue pipe connectors less than nine inches in diameter -
Answer 26 gauge



Oil fired water heater must be equipped with water temp, pressure, and vacuum relief device -
Answer True



Tank vent piping shall be - Answer Pitched forward tank, terminate two feet minimum from
building openings, corrosion resistant weatherproof cap



Direct vent systems shall terminate - Answer 4 feet horizontally from a building opening



Fuel can be transferred from tank to appliance by pressurizing the tank - Answer False



Fusible link safety shutoff valves shall be located - Answer Within six inches of the filter
between the tank and filter



Before installation of new oil burner you are required to - Answer Inspect the combustion
chamber



A crankcase oil burner can be installed in any location where a standard oil burner was located -
Answer False



Can tanks be installed in garages - Answer Yes, if protected from vehicle impacts by barriers



Teflon tape can be used on oil lines - Answer False



The trial for ignition period for oil burners less than 20 GPM is? - Answer 15 seconds



Fusible switches shall operate at a temp of - Answer 165F



A masonry chimney needs a metal liner - Answer False



Any valves used on oil burner installation must be a - Answer Fusible valve



What form is used to pull an oil burner permit - Answer Form 1



What size pipe is used to cross connect tank outlet piping - Answer 1/2 inch

, What is an oil safety valve required - Answer On existing installations when a burner, boiler,
furnace or tank is replaced



When must you install a draft regulator - Answer When not exempted by the manufacturer



As of January 1 2014, max safety timing for an oil burner safety switch must be no more than -
Answer 15 seconds



What type of boiler must be equipped with low water cut off - Answer Water boilers over
400,000 BTU, all steam boiler



What device must be equipped with air proving switch - Answer A draft inducer



New burner controls must be - Answer Interrupted ignition



Hot water boilers need low water cut off if over - Answer 500,000 BTU



How far must continuous concrete slab extend beyond tank perimeter - Answer 8 inches



Can I use any form other than form 1 or form 1A - Answer No, only form 1 and 1A are
approved by state fire Marshall



What must I do if I have a oil tank larger than 10,000 gallons - Answer You must apply for, and
obtain both a permit and license from the local town or city for the use of the tank



What license are acceptable for installing an oil burner or oil tank - Answer M.G.L c. 148, &
10D, and applicable provisions of St. 1964, C. 680 allows for only the holder of certificate of
competency to install oil burner equipment and sign form 1A



Do I need to pull a permit when replacing an oil line or installing an osv - Answer Yes. Any
alteration of oil burner install requires a permit be pulled under CMR 1.00 using form 1 only



Can I cross connect two tanks at bottom with 3/8 pipe tubing - Answer No, cross connecting
must be made with no smaller than 1/2 inch iron pipe or o.d. Tubing

Información del documento

Subido en
5 de julio de 2026
Número de páginas
16
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$12.99

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
COCOSOLUTIONS
4.1
(39)
Vendido
232
Seguidores
16
Artículos
9649
Última venta
23 horas hace




Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes