Medical Gas 6010 Installers |\ |\ |\ |\
Practice Test with answers |\ |\ |\
An existing system that is not in strict compliance with
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
the provisions of this code shall be permitted to be
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
continued in use as long as the _ has determined that |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
such use does not constitute a distinct hazard to life. A)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
architect B) authority having jurisdiction C) engineer D)
|\ |\ |\ |\ |\ |\ |\ |\
nursing staff - CORRECT ANSWERS ✔✔B) authority having
|\ |\ |\ |\ |\ |\ |\
jurisdiction
|\
Cylinder and cryogenic liquid container outlet connections
|\ |\ |\ |\ |\ |\
shall be designed as to render the attachment point _
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
when removal of the outlet connection is attempted. A)
|\ |\ |\ |\ |\ |\ |\ |\ |\
reusable B) unusable C) unsuitable D) universal -
|\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔B) unusable |\ |\ |\
Cylinders in use and in storage shall be prevented from
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
reaching temperatures in excess of _ *F. A) 120 B) 125 C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
130 D) 135 - CORRECT ANSWERS ✔✔B) 125
|\ |\ |\ |\ |\ |\ |\
Nitrous oxide and carbon dioxide using cylinders or
|\ |\ |\ |\ |\ |\ |\ |\
portable containers shall be prevented from reaching
|\ |\ |\ |\ |\ |\ |\
temperatures lower than _ *F A) 130 B)125 C) 20 D) -20 - |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔C)20 |\ |\
,Which of the following systems shall not be permitted to
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
be located in an outdoor enclosure? A) bulk cryogenic
|\ |\ |\ |\ |\ |\ |\ |\ |\
liquid cylinders B) manifolds for gas cylinders C)
|\ |\ |\ |\ |\ |\ |\ |\
manifolds for cryogenic liquid containers D) medical air |\ |\ |\ |\ |\ |\ |\ |\
sources - CORRECT ANSWERS ✔✔D) medical air sources
|\ |\ |\ |\ |\ |\ |\
Indoor locations for oxygen, nitrous oxide, and mixtures of
|\ |\ |\ |\ |\ |\ |\ |\
these gases shall not communicate with any of the
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
following except _? A) area with open flames B) |\ |\ |\ |\ |\ |\ |\ |\ |\
designated storage area C) engines D) kitchens - |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔B) designated storage area |\ |\ |\ |\ |\
Locations for central supply systems shall have _ devices
|\ |\ |\ |\ |\ |\ |\ |\ |\
protected from physical damage? A) electrical B) pressure
|\ |\ |\ |\ |\ |\ |\
indicating C) regulating D) relief - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\ |\
✔✔A) electrical |\
Outdoor locations surrounded by impermeable walls,
|\ |\ |\ |\ |\ |\
except fire barrier walls, shall have protected ventilation
|\ |\ |\ |\ |\ |\ |\ |\
openings at the _ of each wall to allow free circulation of
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
air within the enclosure? A) base B) corner) C) middle D)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
top - CORRECT ANSWERS ✔✔A) base
|\ |\ |\ |\ |\
All positive pressure supply systems shall be provided
|\ |\ |\ |\ |\ |\ |\ |\
with duplex line pressure regulators piped in _? A) circuit
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
,B) loop C) parallel D) series - CORRECT ANSWERS ✔✔C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
parallel
All pressure relief valves shall be made of brass, bronze,
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
or _? A) carbon steel B) cast iron C) copper D) stainless
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
steel - CORRECT ANSWERS ✔✔D) stainless steel
|\ |\ |\ |\ |\ |\
Central supply systems for positive pressure gases shall
|\ |\ |\ |\ |\ |\ |\ |\
have one or more relief valves, the valves shall have a
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
relief setting that is _% above normal working operating
|\ |\ |\ |\ |\ |\ |\ |\ |\
pressure? A) 30 B) 40 C) 50 D) 60 - CORRECT ANSWERS|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
✔✔C) 50 |\
When vented to the outside, relief valve vent lines shall
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
be labeled in which way? A) adhesive markers B) any
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
manner that will distinguish them from the medical gas
|\ |\ |\ |\ |\ |\ |\ |\ |\
pipeline C) stenciling D) stickers - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\
✔✔B) any manner that will distinguish them from the
|\ |\ |\ |\ |\ |\ |\ |\ |\
medical gas pipeline |\ |\
An auxiliary source connection shall consist of all of the
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
following except? A) removable plug or cap B) tee C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
valve D) visual pressure indicator - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\
✔✔D) visual pressure indicator
|\ |\ |\
, In central supply systems using gas or liquid cylinders,
|\ |\ |\ |\ |\ |\ |\ |\ |\
each header shall have a _ to prevent debris from
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
entering the manifold controls? A) check valve B) filter C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
monitor D) relief valve - CORRECT ANSWERS ✔✔B) filter
|\ |\ |\ |\ |\ |\ |\ |\
Manifolds for gas cylinders shall consist of two equal |\ |\ |\ |\ |\ |\ |\ |\ |\
headers, each with enough cylinders for an average day's |\ |\ |\ |\ |\ |\ |\ |\
supply, but not fewer than _ connections? A) 5 B) 4 C) 3
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
D) 2 - CORRECT ANSWERS ✔✔D) 2
|\ |\ |\ |\ |\ |\
Manifolds for gas cylinders shall have a(n) _ signal that |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
visibly indicates the operating status of the equipment
|\ |\ |\ |\ |\ |\ |\ |\
and shall activate an indicator at all master alarm panels
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
when or just before changeover from one header to the
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
other takes place? A) area B) master C) local D) zone -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔C) local |\ |\ |\
When multiple buildings are served from a single
|\ |\ |\ |\ |\ |\ |\ |\
cryogenic liquid oxygen source, it is required to place the |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
emergency oxygen supply connection in _ ? A) each |\ |\ |\ |\ |\ |\ |\ |\ |\
building served B) the building closest to the source C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
the largest building served D) the main building only -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔A) each building served |\ |\ |\ |\ |\
The minimum clearance around EOSC for a temporary
|\ |\ |\ |\ |\ |\ |\ |\
source of supply is _ ft? A) 2 B) 3 C) 5 D) 6 - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔B) 3 |\ |\
Practice Test with answers |\ |\ |\
An existing system that is not in strict compliance with
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
the provisions of this code shall be permitted to be
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
continued in use as long as the _ has determined that |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
such use does not constitute a distinct hazard to life. A)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
architect B) authority having jurisdiction C) engineer D)
|\ |\ |\ |\ |\ |\ |\ |\
nursing staff - CORRECT ANSWERS ✔✔B) authority having
|\ |\ |\ |\ |\ |\ |\
jurisdiction
|\
Cylinder and cryogenic liquid container outlet connections
|\ |\ |\ |\ |\ |\
shall be designed as to render the attachment point _
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
when removal of the outlet connection is attempted. A)
|\ |\ |\ |\ |\ |\ |\ |\ |\
reusable B) unusable C) unsuitable D) universal -
|\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔B) unusable |\ |\ |\
Cylinders in use and in storage shall be prevented from
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
reaching temperatures in excess of _ *F. A) 120 B) 125 C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
130 D) 135 - CORRECT ANSWERS ✔✔B) 125
|\ |\ |\ |\ |\ |\ |\
Nitrous oxide and carbon dioxide using cylinders or
|\ |\ |\ |\ |\ |\ |\ |\
portable containers shall be prevented from reaching
|\ |\ |\ |\ |\ |\ |\
temperatures lower than _ *F A) 130 B)125 C) 20 D) -20 - |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔C)20 |\ |\
,Which of the following systems shall not be permitted to
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
be located in an outdoor enclosure? A) bulk cryogenic
|\ |\ |\ |\ |\ |\ |\ |\ |\
liquid cylinders B) manifolds for gas cylinders C)
|\ |\ |\ |\ |\ |\ |\ |\
manifolds for cryogenic liquid containers D) medical air |\ |\ |\ |\ |\ |\ |\ |\
sources - CORRECT ANSWERS ✔✔D) medical air sources
|\ |\ |\ |\ |\ |\ |\
Indoor locations for oxygen, nitrous oxide, and mixtures of
|\ |\ |\ |\ |\ |\ |\ |\
these gases shall not communicate with any of the
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
following except _? A) area with open flames B) |\ |\ |\ |\ |\ |\ |\ |\ |\
designated storage area C) engines D) kitchens - |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔B) designated storage area |\ |\ |\ |\ |\
Locations for central supply systems shall have _ devices
|\ |\ |\ |\ |\ |\ |\ |\ |\
protected from physical damage? A) electrical B) pressure
|\ |\ |\ |\ |\ |\ |\
indicating C) regulating D) relief - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\ |\
✔✔A) electrical |\
Outdoor locations surrounded by impermeable walls,
|\ |\ |\ |\ |\ |\
except fire barrier walls, shall have protected ventilation
|\ |\ |\ |\ |\ |\ |\ |\
openings at the _ of each wall to allow free circulation of
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
air within the enclosure? A) base B) corner) C) middle D)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
top - CORRECT ANSWERS ✔✔A) base
|\ |\ |\ |\ |\
All positive pressure supply systems shall be provided
|\ |\ |\ |\ |\ |\ |\ |\
with duplex line pressure regulators piped in _? A) circuit
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
,B) loop C) parallel D) series - CORRECT ANSWERS ✔✔C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
parallel
All pressure relief valves shall be made of brass, bronze,
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
or _? A) carbon steel B) cast iron C) copper D) stainless
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
steel - CORRECT ANSWERS ✔✔D) stainless steel
|\ |\ |\ |\ |\ |\
Central supply systems for positive pressure gases shall
|\ |\ |\ |\ |\ |\ |\ |\
have one or more relief valves, the valves shall have a
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
relief setting that is _% above normal working operating
|\ |\ |\ |\ |\ |\ |\ |\ |\
pressure? A) 30 B) 40 C) 50 D) 60 - CORRECT ANSWERS|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
✔✔C) 50 |\
When vented to the outside, relief valve vent lines shall
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
be labeled in which way? A) adhesive markers B) any
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
manner that will distinguish them from the medical gas
|\ |\ |\ |\ |\ |\ |\ |\ |\
pipeline C) stenciling D) stickers - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\
✔✔B) any manner that will distinguish them from the
|\ |\ |\ |\ |\ |\ |\ |\ |\
medical gas pipeline |\ |\
An auxiliary source connection shall consist of all of the
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
following except? A) removable plug or cap B) tee C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
valve D) visual pressure indicator - CORRECT ANSWERS
|\ |\ |\ |\ |\ |\ |\ |\
✔✔D) visual pressure indicator
|\ |\ |\
, In central supply systems using gas or liquid cylinders,
|\ |\ |\ |\ |\ |\ |\ |\ |\
each header shall have a _ to prevent debris from
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
entering the manifold controls? A) check valve B) filter C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
monitor D) relief valve - CORRECT ANSWERS ✔✔B) filter
|\ |\ |\ |\ |\ |\ |\ |\
Manifolds for gas cylinders shall consist of two equal |\ |\ |\ |\ |\ |\ |\ |\ |\
headers, each with enough cylinders for an average day's |\ |\ |\ |\ |\ |\ |\ |\
supply, but not fewer than _ connections? A) 5 B) 4 C) 3
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
D) 2 - CORRECT ANSWERS ✔✔D) 2
|\ |\ |\ |\ |\ |\
Manifolds for gas cylinders shall have a(n) _ signal that |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
visibly indicates the operating status of the equipment
|\ |\ |\ |\ |\ |\ |\ |\
and shall activate an indicator at all master alarm panels
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
when or just before changeover from one header to the
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
other takes place? A) area B) master C) local D) zone -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔C) local |\ |\ |\
When multiple buildings are served from a single
|\ |\ |\ |\ |\ |\ |\ |\
cryogenic liquid oxygen source, it is required to place the |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
emergency oxygen supply connection in _ ? A) each |\ |\ |\ |\ |\ |\ |\ |\ |\
building served B) the building closest to the source C)
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
the largest building served D) the main building only -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔A) each building served |\ |\ |\ |\ |\
The minimum clearance around EOSC for a temporary
|\ |\ |\ |\ |\ |\ |\ |\
source of supply is _ ft? A) 2 B) 3 C) 5 D) 6 - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔B) 3 |\ |\