©The person conducting the fire watch ______ have other duties -
CANNOT
©A portable fire extinguisher with a rating of _________ is required and
should be within ____ feet travel distance hot work area - 2-A:20-
B:C///30
©For ROOFING OPERATIONS, a portable fire extinguisher with a
minimum rating of ______ is required - 3-A:40-B:C
©Fire watch on floors below is ______ - required
©The fire watch must continue for a minimum of ____ minutes after the
hot work is done - 30
©For any CNG or LPG torch operations, the first inspection shall be
conducted ___ minutes after completion. The second inspection shall be
conducted _______ after completion of torch operations. - 30 min///1
hour
©The fire guard or fire watch personnel must complete a signed
inspection report and it must be submitted to and retained by the person
, in charge of the torch operations. - The report must be made available
and maintained on the premises for a minimum of 48 hours after the
work is complete.
©Most common fuel gasses used in blowtorches are ______ - LPG
(butane, propane) natural gas (methane) (either CNG or piped natural
gasses)
©Soldering and brazing temperatures are typically______ - 840 degrees
F
©Oxy-acetylene generates the highest temperature which can reach up
to _____ - 6000 degrees F
©Gas torches can exceed _________ and are used for burning weeds,
melting ice, or applying tar to a roof - 2000 degrees F
©If the torch operation is to stop for a period of _________________,
the torch vale must be closed and the gas supply to the torch must be
completely shut - 1 hour or more
©Containers, valves, regulators, hose and other apparatus and fittings
for oxygen must be kept free of __________. - oil or grease
LEARNING OUTLINE
©The person conducting the fire watch ______ have other duties -
CANNOT
©A portable fire extinguisher with a rating of _________ is required and
should be within ____ feet travel distance hot work area - 2-A:20-
B:C///30
©For ROOFING OPERATIONS, a portable fire extinguisher with a
minimum rating of ______ is required - 3-A:40-B:C
©Fire watch on floors below is ______ - required
©The fire watch must continue for a minimum of ____ minutes after the
hot work is done - 30
©For any CNG or LPG torch operations, the first inspection shall be
conducted ___ minutes after completion. The second inspection shall be
conducted _______ after completion of torch operations. - 30 min///1
hour
©The fire guard or fire watch personnel must complete a signed
inspection report and it must be submitted to and retained by the person
, in charge of the torch operations. - The report must be made available
and maintained on the premises for a minimum of 48 hours after the
work is complete.
©Most common fuel gasses used in blowtorches are ______ - LPG
(butane, propane) natural gas (methane) (either CNG or piped natural
gasses)
©Soldering and brazing temperatures are typically______ - 840 degrees
F
©Oxy-acetylene generates the highest temperature which can reach up
to _____ - 6000 degrees F
©Gas torches can exceed _________ and are used for burning weeds,
melting ice, or applying tar to a roof - 2000 degrees F
©If the torch operation is to stop for a period of _________________,
the torch vale must be closed and the gas supply to the torch must be
completely shut - 1 hour or more
©Containers, valves, regulators, hose and other apparatus and fittings
for oxygen must be kept free of __________. - oil or grease