Escrito por estudiantes que aprobaron Inmediatamente disponible después del pago Leer en línea o como PDF ¿Documento equivocado? Cámbialo gratis 4,6 TrustPilot
logo-home
Document preview thumbnail
Vista previa 2 fuera de 5 páginas
Examen

BACKFLOW PREVENTION STUDY GUIDE (CHARLESTON WATER SYSTEMS)CORRECT 100%

Document preview thumbnail
Vista previa 2 fuera de 5 páginas

Name the two types of backflow. - ANSWERBackpressure and Backsiphonage All of the following may be considered acceptable for containment of a building with the exception of a(n): a) Air Gap b) Double Check Valve Assembly c) Residential Dual Check d) Reduced Pressure Backflow Assembly

Vista previa del contenido

BACKFLOW PREVENTION STUDY
GUIDE (CHARLESTON WATER
SYSTEMS)CORRECT 100%
Name the two types of backflow. - ANSWERBackpressure and Backsiphonage

All of the following may be considered acceptable for containment of a building with the
exception of a(n):
a) Air Gap
b) Double Check Valve Assembly
c) Residential Dual Check
d) Reduced Pressure Backflow Assembly
e) Pressure Vacuum Breaker Assembly - ANSWERe) Pressure Vacuum Breaker
Assembly

A Reduced Pressure Backflow Assembly (RP) protects against:
a) High hazard, Backpressure
b) High hazard, Backsiphonage
c) Low hazard, Backpressure & Backsiphonage
d) All of the above - ANSWERd) All of the above

How many test cocks are on a Reduced Pressure Backflow Assembly? - ANSWER4

How many test cocks are on a Double Check Valve Assembly? - ANSWER4

How many test cocks are on a Pressure Vacuum Breaker Assembly? - ANSWER2

How many test cocks are on an Atmospheric Vacuum Breaker? - ANSWER0

True/False: Test Gauges should be properly stored to ensure they are not damaged
when not in use. - ANSWERTrue

A Backflow Preventer for Beverage Dispensing Equipment protects against carbon
dioxide from entering the potable water supply from which type of backflow?
a) Backpressure
b) Backsiphonage
c) Both A & B
d) None of the above - ANSWERc) Both A & B

A Residential Dual Check Backflow Preventer has:
a) Two Independently Acting Checks
b) Two Independently Acting Checks and an Atmospheric Port
c) Two Independently Acting Checks with a relief valve

, d) None of the Above - ANSWERa) Two Independently Acting Checks

What is the best form or method backflow prevention?
a) A Double Check Valve Assembly
b) A Reduced Pressure Backflow Assembly
c) A Reduced Pressure Detector Assembly
d) An Air Gap - ANSWERd) An Air Gap

A Reduced Pressure Backflow Assembly must be installed:
a) No lower then 12-inches and no higher than 72-inches
b) No lower than 6-inches and no higher than 60-higher
c) Min. 12" or as outlined in the Water Purveyors Cross-Connection Control Program
d) None of the above - ANSWERc) Min. 12" or as outlined in the Water Purveyors
Cross-Connection Control Program

True/False: Atmospheric Vacuum Breakers Protect Against High Hazard. -
ANSWERTrue

True/False: Pressure Vacuum Breakers protect against High Hazard, Backpressure
Applications. - ANSWERFalse

True/False: An Air Gap protects against High Hazard, Backsiphonage Applications. -
ANSWERTrue

True/False: A backflow prevention assembly tester assumes absolutely zero liability
when testing backflow prevention assemblies; only the property owner does. -
ANSWERFalse

True/False: A Pressure Vacuum Breaker must be installed a minimum of 12-inches
above all downstream piping or use. - ANSWERTrue

True/False: Swimming pools, Hospitals, chemical plants, and car washes are all
considered to be high hazard applications. - ANSWERTrue

True/False: Field modifications of any kind to a backflow prevention assembly will void
its approval. - ANSWERTrue

True/False: A Double Check Valve Assembly is appropriate for low hazard only. -
ANSWERTrue

True/False: Continuous pressure is defined as pressure lasting for a period greater than
16 hours within a 24-hour period. - ANSWERFalse

True/False: Atmospheric Vacuum breakers must always be installed in an upright
position and at least 6-inches above all downstream piping for use. - ANSWERTrue

Información del documento

Subido en
12 de febrero de 2026
Número de páginas
5
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$13.99

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
shantelleG
4.0
(118)
Vendido
650
Seguidores
369
Artículos
18317
Última venta
2 días hace




Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes