The minimum rate single fire extinguisher for an Extra Class A hazard
occupancy...
A. 2-A
B. 2-A 10 BC
C. 4-A
D. 4-A 10BC
C. 4-A
The maximum floor area per unit of a rating for an Ordinary Class A Hazard
Occupancy is...
A. 1000 sq ft
B. 1500 sq ft
C. 2000 sq ft
D. 2500 sq ft
A. 1000 sq ft
,The maximum travel distance to an 80-B extinguisher for an Extra B hazard
is...
A. 30 ft
B. 50 ft
C. 75 ft
D. 100 ft
B. 50 ft
The maximum travel distance for a Class C hazard is...
A. 30 ft
B. 50 ft
C. 75 ft
D. none of the above
C. 75 ft
Who is responsible to ensure that proper maintenance, inspection, &
recharging is conducted for all 5 extinguishers in the premises?
A. fire dept
B. authority having jurisdiction
C. ownder
D. service technician
C. owner
, Carbon dioxide hose assemblies that pass the conductivity test shall
have the test information recorded on a label that is attached to the...
A. fire extinguisher
B. carrying handle
C. hose assembly
D. discharge lever
C. hose assembly
Internal examination of the extinguisher is a required procedure during
the annual maintenance for which of the following types of
extinguisher?
A. stored pressure dry chemical
B. cartridge operated dry chemical
C. carbon dioxide
D. none of the above
B. cartridge operated dry chemical
Which of the following types of fire extinguisher does not require a 6
year internal maintenance?
A. cartridge operated dry chemical
B. stored pressure dry powder
C. stored pressure halogenated agent
D. stored pressure water
D. stored pressure water