Electrical Level 3 Module 1 Questions and
Correct Answers
63.55' is the load center distance for a 208V, four-wire, three-
phase branch circuit with fixed
noncontinuous loads from the source of 60A at 45', 40A at 60',
30A at 75', and 25A at 100'. Ans: Here is the solution:
Load 1 = 45' ×60A = 2,700
Load 2 = 60' ×40A = 2,400
Load 3 = 75' ×30A = 2,250
Load 4 =100' ×25A = 2,500
155A 9,850
© 2025 All rights reserved
, 2 | Page
Total load (I) = 155A
Load center length (L) = 9,850
9,850 ÷ 155A = 63.55'
the ampacity of branch circuit conductors must be derated when
there
are more than three current-carrying conductors in a raceway.
Ans: According to the NEC®,
Aluminum THWN - 50A [from NEC Table 310.15(B)(16)]
Correction factor - 0.88 [from NEC Table 310.15(B)(2)(a)]
50A × 0.88 = 44A Ans: ambient temperature of 38°C is 44A. Here
is the solution:
must be derated when installed in conduit on or above rooftops
Ans: Conductors
© 2025 All rights reserved