Relief valve discharges continuously. Problem May be caused by what 5 faults? - ANSWER1. Faulty No. 1 check valve (F1CV) 2. Faulty No. 2 check valve with backpressure (F2CVwB) 3. Faulty relief valve (FRV) 4. Relief valve plugged sensing |ine(s) (RVPSL) 5. Relief Valve leaking diaphragm (RVLD)

Show more Read less
Institution
Backflow Prevention Troubleshooting
Module
Backflow prevention troubleshooting

Content preview

BACKFLOW PREVENTION AND
CROSS CONNECTION CONTROL
CORRECT 100%
Relief valve discharges continuously. Problem May be caused by what 5 faults? -
ANSWER1. Faulty No. 1 check valve (F1CV)
2. Faulty No. 2 check valve with backpressure (F2CVwB)
3. Faulty relief valve (FRV)
4. Relief valve plugged sensing |ine(s) (RVPSL)
5. Relief Valve leaking diaphragm (RVLD)

Relief valve discharges intermittently. Problem May be caused by what 4 faults? -
ANSWER1. Properly working assembly with large pressure fluctuations
2. No.1 check valve reading is close to RV opening point, with small line pressure
fluctuation.
3. Water hammer
4. No. 1 check valve leak with intermittent flow through assembly.

During RP Test 1, Relief Valve discharges after No. 2 shutoff valve is closed. What
does this indicate? - ANSWER1. Normally indicates faulty No. 1 check valve
• Dirty or damaged disc
• Dirty or damaged seat: or,
2. Leak through relief valve diaphragm

During RP Test 1, Relief valve would not open; differential on the field test kit would not
drop. What does this indicate? - ANSWER1. Leaky No. 2 shutoff valve with flow through
the assembly (L2SVwF)

During RP Test 1, Relief valve would not open, differential drops to zero. What does this
indicate? - ANSWER1. Relief valve stuck closed due to corrosion or scale (RVSC).
2. Relief valve sensing line(s) plugged.

During RP Test 1, Relief valve opens too high (with sufficiently high No. 1 check
reading). What does this indicate? - ANSWER1. Faulty relief valve
• Dirty or damaged disc
• Dirty or damaged seat


During PVB Air Inlet Test, Air inlet valve does not open, and reading on field test kit will
not drop. What does this indicate? - ANSWER1. Leaky No. 1 shutoff valve
2. Parallel installation with leaky No. 2 shutoff valve

, During PVB Air Inlet Test, Air inlet valve opens below 1.0 psid, and reading on field test
kit will not drop. What does this indicate? - ANSWER1. Dirty or damaged air inlet valve
disc
2. Scale buildup on seat
3. Damaged spring

During PVB Check Valve Test, Check valve reading below 1.0 psid. What does this
indicate? - ANSWER1. Dirty or damaged check valve disc
2. Dirty or damaged seat
3. Damaged spring

During PVB Check Valve Closing Point Test (Test No. 2), water runs continuously from
test cock No. 2. What does this indicate? - ANSWER1. Leaky No. 1 shutoff valve

During SVB (Either) Test, air inlet valve does not open, as field test kit drops to 0.0 psid.
What does this indicate? - ANSWER1. Air inlet disc stuck to seat
2. Broken or missing air inlet spring
3. Parallel installation with leaky No.2 shutoff valve
4. PVB not SVB

During SVB (Either) Test, Air inlet valve does not open, and reading on field test kit will
not drop. What does this indicate? - ANSWER1. Leaky No. 1 shutoff valve

During SVB (Either) Test, Air inlet opens below 1.0 psid. What does this indicate? -
ANSWER1. Dirty or damaged air inlet disc

During SVB (Check Valve Closing Point) Test 1, Check valve reading below 1.0 psid.
What does this indicate? - ANSWER1. Dirty or damaged check disc
2. Damaged seat
3. Leaking diaphragm/seal

During SVB (Air Inlet Opening Point) Test 2, water runs continuously from vent screw
valve. What does this indicate? - ANSWER1. Leaking No. 1 shutoff valve

What is the purpose and requirement of the RP Test # 1: Relief Valve Opening Point
(USC 10th ed pg 231) - ANSWERPurpose: To test the operation of the differential
pressure relief valve.
Requirement: The differential pressure relief valve must maintain the zone between
the two check valves at least 2 psi less than the supply pressure.

What is the purpose and requirement of the RP Test # 2:Tightness of # 2 Check Valve
(USC 10th ed pg 241) - ANSWERPurpose: To test the # 2 check valve for tightness
against backpressure
Requirement: The # 2 check valve shall be tight against backpressure.

Written for

Institution
Backflow prevention troubleshooting
Module
Backflow prevention troubleshooting

Document information

Uploaded on
February 12, 2026
Number of pages
5
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

£9.69
Get access to the full document:

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF


Also available in package deal

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
shantelleG West Virgina University
Follow You need to be logged in order to follow users or courses
Sold
625
Member since
3 year
Number of followers
369
Documents
18110
Last sold
2 weeks ago
GOLD PREMIUM

HELLO? welcome to my store thanks for visiting this page here you are guaranteed of well revised and assured EXAMS ALL GRADED A+ thus making your education journey easy and seamless . DO NOT HESITATE TO CONTACT ME IF YOU ARE IN NEED OF ANY EXAM .I AM READY 24/7 TO ASSIST YOU ALSO REFER YOUR FRIENDS.

4.0

118 reviews

5
69
4
11
3
24
2
2
1
12

Trending documents

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their exams and reviewed by others who've used these revision notes.

Didn't get what you expected? Choose another document

No problem! You can straightaway pick a different document that better suits what you're after.

Pay as you like, start learning straight away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and smashed it. It really can be that simple.”

Alisha Student

Frequently asked questions