CORE DOMAINS
Refrigeration Theory and Principles
Compressors and Steam Turbines
Heat Exchangers, Condensers, and Evaporators
Refrigerants and Environmental Compliance
Metering Devices and System Accessories
Pumps, Cooling Towers, and Water Systems
Electrical Components and Controls
NYC Fire Code and Building Code Compliance
Safety Procedures and Emergency Response
Recordkeeping and Professional Standards
INTRODUCTION
The FDNY Z-51 Refrigeration Exam assesses the knowledge and competency required to operate,
maintain, and supervise refrigerating systems safely and in accordance with New York City regulations.
This examination evaluates foundational refrigeration theory, applied technical knowledge, regulatory
compliance, ethical responsibilities, and real-world problem-solving abilities. Questions are presented
in multiple-choice and scenario-based formats that emphasize practical application and professional
decision-making. Candidates must demonstrate proficiency across system operations, safety protocols,
environmental standards, and legal requirements. This assessment prepares qualified individuals for
the responsibilities of a Refrigerating System Operating Engineer.
SECTION ONE – QUESTIONS 1–100
Question 1
The most important reason to sub-cool the refrigerant in the condenser is to ensure that:
A. A pure liquid refrigerant will enter the metering device
B. The compressor discharge temperature decreases
,C. System capacity is reduced
D. The evaporator pressure increases
🟢 Correct answer: A
🔴 Explanation: Sub-cooling ensures that refrigerant reaching the metering device is in a completely
liquid state, preventing flash gas from entering the expansion valve and ensuring proper system
operation.
Question 2
A refrigeration engineer is logging readings from a reciprocating system. Compressor discharge
temperatures have dropped significantly and suction line pressure is high. Which condition may be
causing this?
A. A restriction in the liquid line
B. An expansion valve that is open too wide
C. Low refrigerant charge
D. A failed condenser fan
🟢 Correct answer: B
🔴 Explanation: An expansion valve that is open too wide allows excess refrigerant into the
evaporator, raising suction pressure and reducing compressor discharge temperature due to reduced
compression ratio.
Question 3
A low side float valve is used to maintain:
A. The level of refrigerant in the evaporator
B. The compressor discharge pressure
C. The condenser water temperature
D. The oil pressure in the crankcase
🟢 Correct answer: A
🔴 Explanation: A low side float valve maintains a constant liquid refrigerant level in the evaporator by
throttling refrigerant flow based on the liquid level within the evaporator.
Question 4
Regarding fire safety, which ASHRAE refrigerant safety classification indicates no flammability and
lower toxicity?
A. A1
B. A2
C. B1
D. B2
,🟢 Correct answer: A
🔴 Explanation: ASHRAE A1 classification indicates refrigerants with no flame propagation and lower
toxicity, representing the safest classification for refrigerants.
Question 5
When an expansion valve is operating properly, at the end of the evaporator will contain:
A. Only superheated vapor
B. Only saturated liquid
C. A mixture of liquid and vapor
D. Sub-cooled liquid
🟢 Correct answer: A
🔴 Explanation: Proper expansion valve operation maintains evaporator superheat at the outlet,
ensuring that all liquid refrigerant has evaporated and only superheated vapor exits the evaporator.
Question 6
What information is not contained in a Material Safety Data Sheet?
A. Cost of the material
B. Hazardous ingredients
C. First aid measures
D. Physical and chemical properties
🟢 Correct answer: A
🔴 Explanation: MSDS sheets contain safety, health, and handling information but do not include the
cost or pricing of the material.
Question 7
In a steam turbine, what is the function of the Kingsbury thrust bearing?
A. Maintain axial positioning of the rotor shaft
B. Regulate steam admission
C. Control rotational speed
D. Reduce vibration in the coupling
🟢 Correct answer: A
🔴 Explanation: The Kingsbury thrust bearing maintains the axial positioning of the rotor shaft,
preventing axial movement that could cause contact between rotating and stationary components.
Question 8
A centrifugal water pump is considered to be fully primed when:
, A. The pump is full of liquid
B. The discharge valve is fully closed
C. The suction valve is throttled
D. The motor reaches full speed
🟢 Correct answer: A
🔴 Explanation: A centrifugal pump is fully primed when the casing and suction line are completely
filled with liquid, allowing the impeller to develop pressure and move water.
Question 9
Copper tubing refrigerant lines must be installed for a new system. It is well known service practice
that tubing collapses at bends that must be made; the refrigerant engineer should use:
A. Lever-type tubing bender
B. Hammer and anvil
C. Pipe vise and torch
D. Standard pliers
🟢 Correct answer: A
🔴 Explanation: A lever-type tubing bender provides controlled, uniform bending force that prevents
tube collapse or kinking by supporting the tube walls throughout the bend.
Question 10
A reciprocating compressor is making a knocking sound during operation. If worn parts are not
causing the knocking, what is probably the cause?
A. Slugging of liquid refrigerant
B. Low discharge pressure
C. High oil temperature
D. Excessive condenser water flow
🟢 Correct answer: A
🔴 Explanation: Liquid refrigerant slugging occurs when liquid enters the compressor cylinder, causing
hydraulic knocking and potential mechanical damage.
Question 11
In order for a refrigerant to become superheated, it must be heated in a section of the low side
refrigerant line:
A. Where no liquid refrigerant is present
B. Where liquid refrigerant is present
C. Where pressure is increasing
D. Where the refrigerant is sub-cooled