California UST service technician part 2
Approved cathodic protection methods include? - ANS-Sacrificial anodes
Impressed current systems
As of December 22, 1998 singlewall pressured product piping must be constructed of the
following or must be upgraded with secondary containment - ANS-Fiberglass reinforced plastic.
Material compatible with stored product and resistant to corrosion.
Cathodically protected steel.
Cathodic protection systems must be inspected by a certified cathodic protection tester within
___ months of installation - ANS-6
Enhanced line leak detection test methods must be capable of detecting a leak rate of at least?
- ANS-.005 gph
If equipped with overfill alarm the alarm must be triggered to alert the delivery operator when the
tank is no more than____full? - ANS-90%
Motor vehicle fuel tanks include the following EXCEPT: - ANS-Waste oil tanks
Overfill protection is designed to prevent the tank from being over filled during product delivery
by.? - ANS-restricting product flow.
Triggering and audible and visual alarm.
stopping stopping product flow.
Overfill protection was required on all underground storage tanks by? - ANS-December 22,
1998
Persons performingThe annual monitoring certification must possess the following -
ANS-Monitoring equipment manufacturer certification.
Pressured product piping with secondary containment must be subject to an annual pressure
test must be tested with the method capable of detecting a ? - ANS-.1 gph release
results of enhanced Leak Detection testing must be submitted to the local agency and the State
water resources control Board within? - ANS-60 days
Secondary containment test results must be submitted to the local agency within? - ANS-30
days
Single walled suction pipng shall be tested at least every___ years ? - ANS-3 years
Approved cathodic protection methods include? - ANS-Sacrificial anodes
Impressed current systems
As of December 22, 1998 singlewall pressured product piping must be constructed of the
following or must be upgraded with secondary containment - ANS-Fiberglass reinforced plastic.
Material compatible with stored product and resistant to corrosion.
Cathodically protected steel.
Cathodic protection systems must be inspected by a certified cathodic protection tester within
___ months of installation - ANS-6
Enhanced line leak detection test methods must be capable of detecting a leak rate of at least?
- ANS-.005 gph
If equipped with overfill alarm the alarm must be triggered to alert the delivery operator when the
tank is no more than____full? - ANS-90%
Motor vehicle fuel tanks include the following EXCEPT: - ANS-Waste oil tanks
Overfill protection is designed to prevent the tank from being over filled during product delivery
by.? - ANS-restricting product flow.
Triggering and audible and visual alarm.
stopping stopping product flow.
Overfill protection was required on all underground storage tanks by? - ANS-December 22,
1998
Persons performingThe annual monitoring certification must possess the following -
ANS-Monitoring equipment manufacturer certification.
Pressured product piping with secondary containment must be subject to an annual pressure
test must be tested with the method capable of detecting a ? - ANS-.1 gph release
results of enhanced Leak Detection testing must be submitted to the local agency and the State
water resources control Board within? - ANS-60 days
Secondary containment test results must be submitted to the local agency within? - ANS-30
days
Single walled suction pipng shall be tested at least every___ years ? - ANS-3 years