Verified 100% Correct
Source Valve - ANSWER -Shutoff valve at immediate connection of each source
to piped distribution system
Cryogenic Fluid - ANSWER -A fluid with a boiling point lower than -130 deg F
at an absolute pressure of 14.7 psi
Main Line Valve - ANSWER -Shutoff valve in main supply line inside of the
building
200 psi - ANSWER -Instrument air design pressure
Riser Valve - ANSWER -Shutoff valve in each riser adjacent to main line
Service Valve - ANSWER -Shutoff valve in each lateral branch from main or
riser
Zone Valve - ANSWER -Shutoff valves for station outlets and inlets
In-line Valve - ANSWER -Shutoff valves for servicing individual rooms or areas
Diameter Index Safety System - ANSWER -D.I.S.S.
Pin Index - ANSWER -Medaes/Ohmeda/Ohio
Latch Type - ANSWER -Chemetron
Geometric Type - ANSWER -Puritan Bennett
Quick Connect - ANSWER -Schrader
, Primary Valve - ANSWER -Allows user to disconnect equipment without causing
leakage
Secondary Valve - ANSWER -Allows for removal of front assembly for
maintenance and repair without leakage by automatically closing to stop flow of
gas
24 hours - ANSWER -Standing pressure test length
National Institute of Standards and Technology - ANSWER -NIST
23.5% - ANSWER -Oxygen concentration by volume for an oxygen enriched
atmosphere
CGA E-10 - ANSWER -CGA Standard to establish a maintenance program at a
facility
72 in^2 - ANSWER -Minimum free area for louvered openings for natural
ventilation
Demand Check Fitting - ANSWER -Used to facilitate service, testing, or
replacement of all pressure switches and mainline gauges downstream of the
source valve
21 CFR 210 and 21 CFR 211 - ANSWER -FDA Current Good Manufacturing
Practices for bulk liquid oxygen
20 ft - ANSWER -Height above ground for medical air intakes
36 in - ANSWER -Minimum backfilled cover for buried piping
18 in - ANSWER -Minimum backfilled cover for buried piping where physical
damage is otherwise prevented