The maximum test pressure for leak testing a low-pressure centrifugal chiller
is - answer-10 psig
Excessive operation of a purge system means - answer-The system has a
leak on the sub-ambient pressure side of the system
For a commercial refrigeration system with a charge of 50 pounds or more
refrigerant, a substantial (or threshold) week rate will be reduced to ________
after January 1, 2019. - answer-20%
For a comfort cooling system with a charge of 50 pounds or more of
refrigerant, a substantial (or threshold) Leak rate will be reduced to _________
after January 1, 2019. - answer-10%
According to the EPA, when all the R-123 liquid has been removed from an
average 350 ton R-123 chiller and the system vapor pressure is 0 psig, the
system contains - answer-100 pounds of refrigerant in the system
When working with low pressure systems, the high-pressure cut off should
be set to no more than _________ to avoid damaging the system or activating
the pressure blow off device (rupture disk). - answer-10 psig
The rupture discs on the low pressure chiller and on the recovery tank should
relieve at __________ to prevent damage to the system during refrigerant
transfer into or out of the system. - answer-15 psig
If possible, the temperature of the equipment room where the chiller is
located - answer-Should be increased to speed recovery
When possible, oil in the chiller should be heated because - answer-Less
refrigerant will be soluble and/or trapped in the oil at higher temperatures
To prevent freezing, when recharging an evacuated water cooled chiller
system with R-123, first charge with a vapor 20 pressure of at least - answer-
20 in Hg vacuum
When recharging a chiller, refrigerant is first added as a vapor followed by a
liquid refrigerant to avoid - answer-Freezing of the water in the chiller barrels
Replacing _________ is always considered a "major maintenance, service, or
repair"? - answer-1.)An evaporator 2.) Condenser 3.)Compressor