NICET Level 1 exam 2024 with 100% correct answers
When using a pulse load tester on a sealed lead acid battery, the minimum acceptable capacity is... Answer - 80% When a software change is made to a fire alarm system, what percentage of the initiating devices not affected by the change must be tested Answer - 10% When testing elevator recall, the elevator should go to the alternate level when: Answer - The lobby smoke detector on the recall level is activated Minimum requirement for system documentation Answer - Battery calculations/floor plan/sequence of operations/voltage drop calculations Carbon monoxide detectors used for the toxicity of gas fired heating equipment must be tested annually per NFPA 72 Answer - False What is the maximum time period to replace a lead acid battery Answer - Per manufacturers recommendation What type of instrument is normally used to test the specific gravity of lead acid battery cells Answer - Hydrometer Requirements of the branch circuit for the fire alarm control panel Answer - Must be identified as fire alarm circuit.....must have a red marking......must be locked in the ON position if its a circuit breaker A ladder must be able to support ....... Times the weight of the anticipated load Answer - 3.3 times Periodic testing records are req