what are the conditions necessary for good combustion? a) low sulfur content b) Thermal, thermocoupler, tubular c) turbulence, temperature, time 3T's - ANSWERSc) turbulence, temperature, time 3T's why is secondary air necessary in hand fired boilers? a) Necessary to burn the combustible gases b) if primary air should fail c) used only if sulfur content is high - ANSWERSa) Necessary to burn the combustible gases when pressure increases on steam from a given amount of water what happens to its volume and latent heat? a) increases b) decreases c) remains the same - ANSWERSb) decreases when pressure increases on steam from a given amount of water what happens to its temperature? a) increases b) decreases c) remains the same - ANSWERSa) increases when carbon monoxide (co) is formed and carbon dioxide (co2) is very high what does it generally signify? a) More "under the fire air" is needed b) less "under the fire air" is required c) more "over the fire" air is needed d) less "over the fire" is needed less - ANSWERSc) more "over the fire" air is needed excess air is an expression that refers to: a) overabundance of air b) theoretical amount of air c) air supplied above that theoretically required - ANSWERSc) air supplied above that theoretically required

Mehr anzeigen Weniger lesen
Hochschule
MN Boiler License
Kurs
MN Boiler License











Ups! Dein Dokument kann gerade nicht geladen werden. Versuch es erneut oder kontaktiere den Support.

Schule, Studium & Fach

Hochschule
MN Boiler License
Kurs
MN Boiler License

Dokument Information

Hochgeladen auf
13. januar 2026
Anzahl der Seiten
37
geschrieben in
2025/2026
Typ
Prüfung
Enthält
Fragen & Antworten

Themen

Inhaltsvorschau

MN Boiler License Questions with
Accurate Answers

what are the conditions necessary for good combustion?
a) low sulfur content
b) Thermal, thermocoupler, tubular
c) turbulence, temperature, time 3T's - ANSWERSc) turbulence, temperature, time 3T's

why is secondary air necessary in hand fired boilers?
a) Necessary to burn the combustible gases
b) if primary air should fail
c) used only if sulfur content is high - ANSWERSa) Necessary to burn the combustible
gases

when pressure increases on steam from a given amount of water what happens to its
volume and latent heat?
a) increases
b) decreases
c) remains the same - ANSWERSb) decreases

when pressure increases on steam from a given amount of water what happens to its
temperature?
a) increases
b) decreases
c) remains the same - ANSWERSa) increases

when carbon monoxide (co) is formed and carbon dioxide (co2) is very high what does it
generally signify?
a) More "under the fire air" is needed
b) less "under the fire air" is required
c) more "over the fire" air is needed
d) less "over the fire" is needed less - ANSWERSc) more "over the fire" air is needed

excess air is an expression that refers to:
a) overabundance of air
b) theoretical amount of air
c) air supplied above that theoretically required - ANSWERSc) air supplied above that
theoretically required

a good percentage of carbon dioxide when burning oil is:
a) 12%

,b) 8 %
c) 10% - ANSWERSa) 12%

what is draft on a boiler in operation?
a) Flow of gases through boiler
b) difference in pressure between atmosphere and furnace or firebox
c) difference between atmospheric pressure and breeching - ANSWERSb) difference in
pressure between atmosphere and furnace or firebox

which has greater heating value per pound?
a) oil
b) coal - ANSWERSa) oil (18000 - 19500 BTU)
(coal has (6900 - 12910 BTU))

heavy oil must be heated before entering the burner to:
a) increase carbon content
b) decreased sulfur content
c) get proper atomization - ANSWERSc) get proper atomization

why should a daily log be kept of flue gas temperature?
a) Valuable information in case of explosion
b) superintendent files them
c) change an operation, causing heat loss, can be detected - ANSWERSc) change an
operation, causing heat loss, can be detected

find SWP of a boiler 72 inches in diameter, thickness of one-half inch, tensile strength of
55,000 pounds, quadruple riveted butt and strap joint (.94) factor of safety 5:
a) 14.3
b) 143.6
c) 1436 - ANSWERSb) 143.6

the total heat of steam is 1,188 BTUs, and feed water temperature is 182 degrees
Fahrenheit. What is the factor of evaporation?
a) 107
b) 10.7
c) 1.07 - ANSWERSc) 1.07

why would viscosity be important in fuel oil?
a) more heat is recovered in water
b) has more volatile hydrocarbons
c) affects ease with which it can be handled - ANSWERSc) effects ease with which it
can be handled

why is too much air objectionable?
a) Cost too high
b) loss of efficiency

,c) corrosive effect - ANSWERSb) loss of efficiency

what is a fyrite used for?
a) flue gas analyzer
b) combustion programmer
c) water analysis - ANSWERSa) flue gas analyzer

absolute pressure is (ABS):
a) atmospheric pressure - gauge pressure
b) gauge pressure minus atmospheric pressure
c) atmospheric pressure + gauge pressure - ANSWERSc) atmospheric pressure +
gauge pressure

when pressure of steam increases, what happens to the temperature?
a) Goes up
b) goes down
c) remains the same - ANSWERSa) Goes up

find the square feet of heating surface of a flu 4" in diameter and 20' in length:
a) 25'sq
b) 251.32'sq
c) 2513'sq
d) 20.93'sq - ANSWERSd) 20.93'sq

what is the minimum size of the pipes connecting the boiler to the water column?
a) 3/4 inch
b) 1 inch
c) 1/2 inch - ANSWERSa) 3/4 inch

why are crosses used instead of ells on water column connections?
a) Cost less
b) has more strength
c) line may be easily cleaned - ANSWERSc) line may be easily cleaned

can you have valves between boiler and water column?
a) Yes, if they are locked or sealed open
b) no, they might be closed accidentally
c) only if the boiler is under 100 horsepower - ANSWERSa) Yes, if they are locked or
sealed open

can you have valves between boiler and water column?
a) Yes, if they are locked or sealed open
b) no, they might be closed accidentally
c) only if the boiler is under 100 horsepower - ANSWERSa) Yes, if they are locked or
sealed open

, in the HRT boiler, the fuse plug is located in the rear head, _____ inches above the top
row of tubes.
a) 2"
b) 1/2"
c) 1" - ANSWERSa) 2"

a siphon coil (pigtail) is employed in steam gauge line protects the :
a) Bourdon tube
b) piping
c) draft gauge - ANSWERSa) Bourdon tube

what type of shut off would be preferable on a pressure gauge valve that is not used
a) non-return
b) needle-type
c) cock with a T or lever-type handle - ANSWERSc) cock with a T or lever-type handle

steam gauges shall have a dial graduation of at least:
a) 1 1/2 times the M.A.W.P.
b) same pressure as the boilers
c) 2.0 times the M.A.W.P. - ANSWERSa) 1 1/2 times the M.A.W.P.

what is the function of a feed water regulator?
a) controls temperature of water
b) control solids in the water of boiler
c) control water level in a boiler - ANSWERSc) control water level in a boiler

when two stop valves are used on a steam outlet line, it is good practice to have one
valve :
a) slow opening
b) automatic non-return
c) quick opening - ANSWERSb) automatic non-return

is the valve stem connected to the disc on an automatic non-return valve?
a) no
b) yes
c) only when open - ANSWERSa) no

what must you have between two stop valves on the steam outlet and between the
header line?
a) thermocoupler
b) dial actuated thermostat
c) drain - ANSWERSc) drain

on a globe valve used on feed piping, the inlet shall be:
a) immaterial
b) above the valve disc

Lerne den Verkäufer kennen

Seller avatar
Bewertungen des Ansehens basieren auf der Anzahl der Dokumente, die ein Verkäufer gegen eine Gebühr verkauft hat, und den Bewertungen, die er für diese Dokumente erhalten hat. Es gibt drei Stufen: Bronze, Silber und Gold. Je besser das Ansehen eines Verkäufers ist, desto mehr kannst du dich auf die Qualität der Arbeiten verlassen.
Bestgrades2 West Virginia University
Folgen Sie müssen sich einloggen, um Studenten oder Kursen zu folgen.
Verkauft
23
Mitglied seit
1 Jahren
Anzahl der Follower
0
Dokumente
4142
Zuletzt verkauft
3 Jahren vor

4,0

3 rezensionen

5
1
4
1
3
1
2
0
1
0

Kürzlich von dir angesehen.

Warum sich Studierende für Stuvia entscheiden

on Mitstudent*innen erstellt, durch Bewertungen verifiziert

Geschrieben von Student*innen, die bestanden haben und bewertet von anderen, die diese Studiendokumente verwendet haben.

Nicht zufrieden? Wähle ein anderes Dokument

Kein Problem! Du kannst direkt ein anderes Dokument wählen, das besser zu dem passt, was du suchst.

Bezahle wie du möchtest, fange sofort an zu lernen

Kein Abonnement, keine Verpflichtungen. Bezahle wie gewohnt per Kreditkarte oder Sofort und lade dein PDF-Dokument sofort herunter.

Student with book image

“Gekauft, heruntergeladen und bestanden. So einfach kann es sein.”

Alisha Student

Häufig gestellte Fragen