- 1. What is the primary standard governing the installation, testing, and maintenance of fire alarm systems in the United States? 
ANSWER: NFPA 72, National Fire Alarm and Signaling Code. 
 
2. According to NFPA 72, what is the maximum allowable air velocity past a spot-type smoke detector? 
ANSWER: The maximum air velocity shall not exceed 300 ft/min (1.5 m/s) for ceiling-mounted detectors. 
 
3. A manual fire alarm box (pull station) must be installed at a height of _____ above the finished flo...
-
$12.41 Meer Info
Vintage
-
Tentamen (uitwerkingen)
TFM 12 FIRE ALARM TECHNICAL ACTUAL EXAM 2024 WITH EXPERTISE FEEDBACK. NEW
-
---11februari 20242023/2024A+
- TFM 12 FIRE ALARM TECHNICAL ACTUAL 
EXAM 2024 WITH EXPERTISE FEEDBACK. 
NEW 
Does a fire hood system and a kitchen need to be monitored by the fire alarm 
system? 
Yes 
What does P.L.F.A stand for? 
Power Limited Fire Alarm 
What does N.P.L.F.A stand for? 
Non-Power Limited Fire Alarm 
What is the difference between P.F.L.A and N.P.F.L.A? 
an N.P.L.F.A can operate at up to 600v, and the power output isn't limited 
a P.L.F.A has the voltage and power limited by a listed power source. 