A PFAS includes a full-body harness, a shock-absorbing lanyard and a secure anchorage point
capable of supporting __________ pounds 5000
Use a minimum _________ AWG green insulated ground wire telecommunications equipment-
bonding conductor to bond cabinets and racks. 6
Clearance from the bottom of the access floor tile to the top of the cable tray or other raceway
shall be at least ______ inches to permit cable bundles and innerduct to exit out the top of the
tray without incurring damage 2
Allow no more than_____ of conduit and bushing to extend into the room 3"
Light, as measured within the TE, should be a minimum of _________ lux. 538 lux (or 50
foot candles)
If FMC must be used, limit the length to ________ 20 feet
Toggle bolts should be installed __________ inches from the edges of the sheet of plywood
2
, When securing equipment to a cabinet or rack, there are 4 popular thread sizes for mounting
screws, what ate they? M5
M6
12-24
10-32 (4-10)
The minimum recommended separation distance that telecommunications cabling should be
kept from High-intensity discharge lamps is ________ 6"
The "B" in "ABC" stands for Breathing
________ milliamperes produce a painful shock, and the muscles cannot release the contact
10 (3-22)
In the absence of a specified distance, plan for a minimum of _______ work and aisle space
between and around equipment. 1 meter
For ICT systems use, grade _______ plywood should be used A/C
Generally start mounting plywood ______ inches above finished floor 8
Allow no more than _____ of conduit and bushing to extend into the room. 3"