ACTUAL Questions and CORRECT
Answers
Secondary containment required for all new USTs (date) - CORRECT ANSWER -
January 1, 1984
(25291; H&SC)
23 CCR closure requirements do not apply to UST closed prior to ____________________
(date) - CORRECT ANSWER - January 1, 1984
(2670(I); CCR)
New UST with pressured piping must have secondary containment after
__________________(date) - CORRECT ANSWER - July 1, 1987
(25291; H&SC)
Spill Containment required for all USTs (date) - CORRECT ANSWER - December 22,
1998
(2665; CCR)
Overfill protection required for all USTs (date) - CORRECT ANSWER - December 22,
1998
(2665; CCR)
, Secondary Containment required for all non-motor vehicle fuel USTs (date) - CORRECT
ANSWER - December 22, 1998
(2662 (b); CCR)
Striker Plates required (date) - CORRECT ANSWER - December 22, 1998
(2662; CCR)
Single wall steel USTs required cathodic protection & lining or bladder (date) - CORRECT
ANSWER - December 22, 1998
(2662 (c); CCR)
Shut down and fail safe LLDs required for single wall pressurized piping (date) - CORRECT
ANSWER - December 22, 1998
(2666 (c); CCR)
Under Dispenser Containment (UDC) required for newly installed USTs (date) - CORRECT
ANSWER - January 1, 2000
(2636 (g); CCR)
An individual installing UST components manufacturer's refresher training required (date) -
CORRECT ANSWER - July 1, 2001
(2715 (g)(1); CCR)