Where optical fibers are utilized for fire alarm circuits, the cables
shall be installed in accordance with _ _.
NEC Art. 760.3(F)
NEC Article 770
An insulated grounded conductor of _____ or smaller must be
identified with a continuous white outer finish.
NEC Art. 200.6(A)
6 AWG
,Where a spot-type smoke detectors is installed during
construction, it shall___ _.
not be operational, and protected from construction debris, dust,
dirt and damage.
What is the ohm value of a resistor with the following color band:
Red, Green, Orange and no tolerance band.
25,000 ohms
Sampling system piping shall be conspicuously identified as
"SMOKE DETECTOR SAMPLING TUBE - DO NOT DISTURB", at
intervals on piping that provide visibility within the space, but not
greater than _.
20'ft
,A 24VDC bell draws 0.8 amps of current and it is located 500'ft
from the fire alarm control panel. According to the manufacturer,
the bell will operate with no more than a 10% voltage drop.
Assuming a temperature of 70*F, what is the smallest sized, coated
solid copper conductor that shall be used to provide power to the
bell?
-Find Chapter 9 table 8 in the NEC, plug ohm values into your
equation E = I*R and solve
12 AWG
According to NFPA 72, strobe lights shall not ____ _.
Exceed 2 flashes per second (2Hz)
, The branch circuit supplying the fire alarm equipment shall __ _.
supply no other loads
A circuit contains 2 resistors connected in series. When 24VDC are
applied to the circuit, 2.4 amps of current are drawn. What is the
total resistance of the circuit?
-R = E/I
10 ohms
Worn or frayed electric cords or cables shall ____ _.
be disposed of properly
Fire alarm storage batteries shall_____ _.
be either trickle or float-charge
Rod and pipe grounding electrodes shall not be less than ___ in
length.
8'ft